Diagnostic Procedure for Check Code
Check code
[d1]
Master outdoor unit setup alarm
Are there multiple inverter
outdoor units connected?
No
Is setup of the master
outdoor units at center
position duplicated?
[Set SW08 bit 2 on
interface P .C. board of
each unit.(*1)]
No
Check interface P .C. board.
( *1) Setup of outdoor unit at center position (SW08 bit 2 setup on outdoor interface
P .C. board)
OFF: Server/ON: Master (Automatic setup for inverter outdoor unit)
Troubleshooting
1. No. of connected inverter outdoor units
2. Incorrect setup of master outdoor unit
3. Defective outdoor interface P .C. board
Yes
Yes
85
Operation cause
Set only one inverter
outdoor unit per system.
Set only one unit as master,
turn off all source power,
and then restart the operation.