Toshiba MM-A0280HT Service Manual page 79

Modular multi split type system
Hide thumbs Also See for MM-A0280HT:
Table of Contents

Advertisement

TD1 condition gas leak detection
Are the gas pipe and liquid
pipe service valves of the
outdoor unit fully open?
Is there a blockage
in the PMV assembly on
the liquid line?
Is the cooling bypass
PMV B normal?
Are the resistance characteristics
of TD1 sensor normal?
Is the wiring correct?
14
Insufficient refrigerant,
blockage, pipe breakage.
There is an abnormal power phase order or missing phase of power supply to the outdoor
unit. Check power supply wiring.
Troubleshooting
Diagnostic Procedure for Check Code
Check code
[AE]
No
Yes
Yes
No
No
Yes
No
Yes
No
Yes
(Check miswiring of the outdoor unit according to miswiring check function.)
Check code
[AF]
Phase order alarm
Operation cause
1. Outdoor unit service valve closed
2. Cooling bypass PMV error
3. TD1 sensor error
4. Insufficient refrigerant, blockage in pipe
5. Blockage of indoor filter
6. Blockage of PMV assembly on the liquid line
Operation cause
Abnormal power phase order or missing phase of
power supply to the outdoor unit
80
Open valves fully.
Replace both the PMVs.
Cooling bypass PMV B error
Replace TD1 sensor.
Set normal wiring.