Toshiba MM-A0280HT Service Manual page 48

Modular multi split type system
Hide thumbs Also See for MM-A0280HT:
Table of Contents

Advertisement

Self Diagnostic Display Information
(5) Outdoor unit information data display (Displayed on inverter unit only)
SW03 SW02 SW01
1 to 3 1 to 16
4
Indoor communication/
Receive status
5
Indoor check code
6
Indoor horse power
7
Indoor demand
command (S code)
8
Indoor PMV opening
9
Indoor saturation temp.
10
Indoor TA sensor
11
Indoor TC2 sensor
12
Indoor TC1 sensor
NOTE: The indoor address number is set by selecting SW02 or SW03.
SW03
SW02
1
1 to 16
2
1 to 16
3
1 to 16
• 7 segment display A, B
Outdoor Units
A
[01] to [48]: Indoor address number
B
[ 1]: Receiving, [– –]: No connection
A
[01] to [48]: Indoor address number
B
[– –]: No error, a check code is displayed when an error
occurs.
A
A [01] to [48]: Indoor address number
B
Corresponded HP is displayed. ([– –]: No connection)
[0, 8], [ 1], [1, 2], [1, 5], [1, 7], [ 2]
[2, 5], [ 3], [3, 2], [ 4], [ 5]
A
[01] to [48]: Indoor address number
B
[ 0]: In STOP time, [ 3] to [ F]: During operation (S3 to SF)
A
[01] to [48]: Indoor address number
B
Data is displayed as pulse
A
[01] to [48]: Indoor address number
B
Data is displayed as temperature
A
[01] to [48]: Indoor address number
B
Data is displayed as temperature
A
[01] to [48]: Indoor address number
B
Data is displayed as temperature
A
[01] to [48]: Indoor address number
B
Data is displayed as temperature
Outdoor unit number
SW02 setup number
SW02 setup number + 16
SW02 setup number + 32
Display A
D716
D717
49
Displayed content
7 segment display A
Display B
D714
D715
[01] to [16]
[17] to [32]
[33] to [48]
12