The input rate for the Concept boiler, on Direct Vent or
Category IV installations, may be set up to a maximum of
15% above to 25% below the nominal specified rating plate
input of each model. See Chart 1. This allowance is useful in
better sizing the boiler's input rate to each installation site's
heat load.
The input rate for the Concept boiler, on Category I
installations, must only be set to one specified input rate for
each model. See Chart 2. This rate, which is typically higher
than the nominal specified rating plate input for each model
(except the CB-180), will ensure that a high enough flue
temperature is obtained to safeguard against condensation
forming in the flue piping and chimney stack. On all Category
I installations, the air pressure switch provided on the boiler
must be replaced with the switch provided in vent kit 665194.
This switch is set to prevent the boiler from operating below
the approved Category I input rate.
Chart 1:
Input Rate Adjustment Specifications for Direct Vent and Category IV Installations
CB-45
w
BTUH
9 890
33,750
10 550
36,000
11 210
38,250
11 870
40,500
12 530
42,750
13 190
45,000
13 850
47,250
14 510
49,500
15 170
51,750
* Follow instruction manual operation procedures, Step C, to set with meter. Ability to attain input rates over the nominal rating plate specifications
may be constrained by installation variables such as vent length, altitude, and calorific value of the gas, particularly on the larger models of boilers.
† Follow instruction manual operation procedures, Step A, to set with gauge.
Chart 2:
This chart must be used for Input Rate Adjustment for Category I Installations
Boiler
Category I Input Rate *
Model
w
CB-45
16 120
CB-90
30 480
CB-135
42 500
CB-180
52 760
* Follow instruction manual operation procedures, Step C, to set with meter.
† Follow instruction manual operation procedures, Step A, to set with gauge.
Provisions for combustion and ventilation air must be made in accordance with Section 5.3, air for combustion and ventilation, CSA 149.1-00 for
natural gas and propane..
20

Input Rate Adjustment Specifications

Boiler Model and Allowable Input *
CB-90
w
BTUH
w
19 780
67,500
29 670
21 100
72,000
31 650
22 420
76,500
33 630
23 740
81,000
35 610
25 060
85,500
37 590
26 380
90,000
39 570
27 700
94,500
41 550
29 020
99,000
43 530
30 340
103,500
45 510
Differential Pressure †
BTUH
mm w.c.
55,000
25.40
104,000
21.59
145,000
19.05
180,000
16.51
To set the input rate of the Concept boiler perform the
following adjustment procedure:
A. Refer to the Operation Procedures on pages 18 and 19
which specify the methods of calibrating the boiler'
components for proper input rate and air/gas ratio.
B. Note that Step A and Step C are followed to set rate only
depending on whether a differential pressure gauge or a
gas meter is available. Either method is adequate to se
input, or both can be performed as a verification of inpu
rate. Use these procedures, in conjunction with the
appropriate chart below, to adjust the input rate a
specified for that venting application.
C. Note that Step B is followed to set the air/gas ratio only
not to set input rate. Follow Step B precisely as specified
in the instruction manual.
CB-135
CB-180
BTUH
w
101,250
39 560
108,000
42 200
114,750
44 840
121,500
47 480
128,250
50 120
135,000
52 760
141,750
55 400
148,500
58 040
155,250
60 680
Air Flow
Percent of increase
over nominal boiler
input rate
in. w.c.
1.00
.85
.75
.65
Air Flow
Differential
Pressure †
BTUH mm w.c.
in.w.c.
135,000
10.67
.42
144,000
12.19
.48
153,000
13.72
.54
162,000
15.49
.61
171,000
17.27
.68
180,000
19.05
.75
189,000
21.08
.83
198,000
23.11
.91
207,000
25.15
.99
22%
15%
7%
0%
Percent of change
to nominal boiler
input rate
Reduced by 25%
Reduced by 20%
Reduced by 15%
Reduced by 10%
Reduced by 5%
Nominal 0%
Increased by 5%
Increased by 10%
Increased by 15%

Hide quick links: