Slant/Fin LX-90 Installation And Operating Instructions Manual

Slant/Fin LX-90 Installation And Operating Instructions Manual

Direct-vent sealed combustion condensing boiler hot water
Hide thumbs Also See for LX-90:

Advertisement

LYNX
DIRECT-VENT SEALED COMBUSTION CONDENSING BOILER
HOT WATER MODEL LX-90, LX-120 & LX-150
GAS-FIRED BOILERS FOR NATURAL AND L.P. PROPANE GASES
INSTALLATION AND OPERATING INSTRUCTIONS

TABLE OF CONTENTS

Dimensions, Rating and Orifice Sizes ........................................2
Identification of Parts ........................................................................3
Installation Requirements .................................................................4
Contamination Prevention.................................................................5
Mounting the boiler on a wall............................................................6
Venting Application ...........................................................................6
Boiler Room Air Supply and Ventilation............................................6
Flue Gas Venting Requirements.......................................................7
Vent and Air Intake Material .............................................................8
PVC/CPVC Pipe General Assembly Method....................................8
Vent and Air Intake Restrictions .......................................................8
Sidewall Venting, Non-Direct Vent ..................................................10
Vent Termination Location and Clearance......................................10
Non-Direct Vent Installation ............................................................10
Direct Vent Installation ....................................................................10
Sidewall Venting, Direct Vent ..........................................................10
Vent/Air Intake Termination Installation...........................................16
Venting and Air Intake Regular Inspection .....................................18
Condensate Removal System ........................................................18
Gas Piping ......................................................................................18
Electrical Wiring ..............................................................................19
Wiring Diagram ...............................................................................20
Single and Multi Zoning ..................................................................22
Water Piping ...................................................................................24
Operating Instructions.....................................................................30
Boiler Control and Display ..............................................................30
Boiler Operating Status ..................................................................31
Viewing and changing temperature ................................................32
Viewing and changing system setting ............................................33
Initial start and operating instruction ..............................................35
Sequence of Operation...................................................................36
Combustion check and fuel input rate ............................................37
Safety Check .................................................................................37
Diagnostic error codes ...................................................................38
Care and Maintenance ...................................................................41
General Troubleshooting Guide ......................................................42
The venting system of this boiler is under positive pressure.
Leakage from this system can be hazardous and if not avoided
can result in death or serious injury. In addition to the recommen-
dations within this manual and the User's Information Manual, the
venting system, from the flue collector to the outdoor discharge,
must be carefully checked annually by a qualified service agency.
Heating Contractor
Address
Phone Number
Printed in U.S.A. 413
WARNING
This manual must be left with owner and should be hung
on or adjacent to the boiler for reference.
IMPORTANT
READ ALL OF THE FOLLOWING
WARNINGS AND STATEMENTS
BEFORE READING THE
INSTALLATION INSTRUCTIONS
LIQUEFIED PETROLEUM (L.P.)
PROPANE GAS-FIRED BOILERS
Installation location ONLY as permitted in paragraph
entitled "LIQUEFIED PETROLEUM (L.P.) PROPANE
GAS-FIRED BOILER LOCATION" on page 5 of this
instruction book.
The above warning does not apply to NATURAL
gas fired boilers.
The installation must conform to the requirements of
the authority having jurisdiction or, in the absence of
such requirements, to the National Fuel Gas Code,
ANSI Z223.1-latest edition. The installation must also
conform to the additional requirements in this Slant/Fin
Instruction Book.
In addition where required by the authority having juris-
diction, the installation must conform to American
Society of Mechanical Engineers Safety Code for
Controls and Safety Devices for Automatically Fired
Boilers, No. CSD-1.
This boiler, gas piping and accessories must be
installed, connected, serviced and repaired by a
trained, experienced service technician, familiar with all
precautions required for gas-fired equipment and
licensed or otherwise qualified, in compliance with the
authority having jurisdiction.
Boiler Model Number
Boiler Serial Number
Installation Date
Part No. 81-5001000
WARNING
WARNING
Publication No. LX1-40 Rev. F

Advertisement

Table of Contents
loading

Summary of Contents for Slant/Fin LX-90

  • Page 1: Table Of Contents

    This manual must be left with owner and should be hung on or adjacent to the boiler for reference. DIRECT-VENT SEALED COMBUSTION CONDENSING BOILER HOT WATER MODEL LX-90, LX-120 & LX-150 GAS-FIRED BOILERS FOR NATURAL AND L.P. PROPANE GASES INSTALLATION AND OPERATING INSTRUCTIONS...
  • Page 2: Dimensions, Rating And Orifice Sizes

    LEFT SIDE FRONT RIGHT SIDE BOILER "A" "B" "C" "D" MODEL BOILER "A" "B" "C" "D" LX-90 6 3/4 3 3/8 2 3/4 16 1/4 MODEL LX-120 6 5/8 3 3/8 16 1/4 LX-90 6 3/4 3 3/8 2 3/4...
  • Page 3: Identification Of Parts

    Lynx LOCATION AND IDENTIFICATION OF PARTS BOILER BOILER BOILER CONTROL RETURN SUPPLY UNDER THE COVER WATER WATER INTAKE VENT GAS SUPPLY TURN VALVE BLACK SCREW 1/4 TURN THEN LIFT CONTROL COVER TO REMOVE PRESSURE GAUGE MODE DISPLAY POWER SWITCH TEMPERATURE AIR INTAKE DISPLAY HOSE...
  • Page 4: Installation Requirements

    MINIMUM ALCOVE AND CLOSET CLEARANCE For Combustible Recommended This installation must also conform to the additional require- Surface Construction for Service ments in this Slant/Fin Instruction Book. Front 6" 18" Rear 0" 0" BOILER LOCATION Left Side 0"...
  • Page 5: Contamination Prevention

    Lynx CONTAMINATION PREVENTION The combustion air supply must not be susceptible to contami- nation sources, whether the combustion air comes from the interior or exterior of the building. Contaminated air can cause corrosion or other damage to the heat exchanger and compo- nents of the boiler, causing failure of these parts or unsafe operation.
  • Page 6: Mounting The Boiler On A Wall

    Lynx MOUNTING THE BOILER ON A WALL Lift the boiler up against the wall, with the top edge of the jacket slightly above the wall bracket tabs. There are 2 Be sure that the wall is vertically plumb and capable of carrying holes in the upper corners of the jacket rear panel, that the weight of the boiler and the system piping, when full of can visually be aligned with the 2 larger diameter holes in...
  • Page 7: Flue Gas Venting Requirements

    Lynx A. NON-DIRECT VENT INSTALLATION ADDITIONAL REQUIREMENTS FOR THE COMMONWEALTH 1. Air drawn horizontally from outdoors DIRECTLY through OF MASSACHUSETTS an outside wall; one louvered opening near the floor and When the Bobcat is installed and used in the Commonwealth of Massa- one louvered opening near the ceiling, each opening with a chusetts, the following additional requirements pursuant to Massachusetts minimum FREE air passage area of 1 square inch per 4000...
  • Page 8: Vent And Air Intake Material

    Lynx PVC/CPVC PIPE GENERAL ASSEMBLY METHOD VENT AND AIR INTAKE MATERIALS The following are the recommended methods for cutting, The vent and air intake system for direct or non-direct vent instal- cleaning and connecting PVC and CPVC pipe, for both the lation must be 3”...
  • Page 9 Lynx 6. The Lynx boiler is equipped with a built-in condensation drain and trap. The trap must be filled with water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. The drain must dispose of possibly large quantities of condensate, which may require a neutralizing system.
  • Page 10: Sidewall Venting, Non-Direct Vent

    Only these 2 models of vent/air intake termination are any forced air inlet located within 10 feet. approved for this method of installation. Refer to the Slant/Fin boilers Parts List (publication number LXA-10PL) for the appro- 2. The venting system shall terminate at least 12 inches priate model for the vent material to be used.
  • Page 11 Lynx NON-DIRECT VENT, SIDEWALL VENTING All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” nominal ID polypropylene pipe or U/L listed single wall 3" dia. AL29-4C S.S.*. venting materials (See page 7). Figure 7. Non-direct vent, side wall venting - utilizing PVC/CPVC or polypropylene pipe for venting. Figure 8.
  • Page 12 Lynx NON-DIRECT VENT, VENTING THROUGH A ROOF All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” nominal polypropylene pipe or U/L listed single wall 3" dia. AL29-4C S.S.*. venting materials (See page 7). POLYPROPYLENE Figure 9.
  • Page 13 Lynx NON - DIRECT VENT, UTILIZING AN EXISTING CHIMNEY AS A CHASE All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” ID polypropylene or U/L listed single wall 3" dia. AL29-4C S.S.*. venting materials (See page 7). POLYPROPYLENE Figure 10.
  • Page 14 Lynx DIRECT VENT, SIDEWALL VENTING All joints must be liquid and pressure tight. Use 3” dia. PVC/CPVC schedule 40 pipe, 3” nominal ID polypropylene or U/L listed single wall 3" dia. AL29-4C S.S.*. venting materials (See page 7). OR POLYPROPYLENE OR POLYPROPYLENE Figure 11.
  • Page 15 (SNORKEL STYLE) Lynx BIRD SCREEN 12" MIN. 16" MAX. AIR INTAKE PIPE FLUE PIPE 12" MIN. BIRD SCREEN 12" MAX. Figure 12a. Sidewall venting and air intake piping (snorkel style) Figure 13b. Vent/Air intake termination; utilizing stainless steel venting materials. Knowledge of local conditions will revel the maximum height that repeated Figure 13a.
  • Page 16: Vent/Air Intake Termination Installation

    Lynx VENT/AIR INTAKE TERMINATION FOR PVC/CPVC, OR POLYPROPYLENE VENTING INSTALLATION (P# 840802000) VENT/AIR INTAKE TERMINATION FOR STAINLESS STEEL VENTING INSTALLATION (P# 840804000) This termination is designed specifically for 3” diameter PVC, CPVC Schedule 40 or polypropylene pipe to be used as the This termination is designed specifically for Heat-Fab Saf-T vent and air intake piping material, only.
  • Page 17: Direct Vent, Venting And Air Intake Through A Roof

    Lynx B. DIRECT VENT - VENTING AND AIR INTAKE For PVC/CPVC pipe, follow the proper assembly practices THROUGH A ROOF specified on page 8, and venting system restrictions specified on page 8 of this manual. For stainless steel venting systems, follow the vent manufacturer’s instructions and the restrictions Figure 14 shows typical vertical venting.
  • Page 18: Venting And Air Intake Regular Inspection

    Lynx above 6.5, which is safe for all drain piping materials. (See Figure VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTION 15). The neutralizing filter medium will require periodic changing, A. Inspect the system regularly for condensation, corrosion, to ensure it’s affectiveness. Replacing the medium on an annual sagging and/or physical damage.
  • Page 19: Electrical Wiring

    Lynx At 30 ft. length of pipe, match required capacity from table on Boiler must be electrically grounded in accordance with the this page (choose higher capacity, in this case is 152 cu. ft. per requirements of the authority having jurisdiction, or, in the hour).
  • Page 20: Wiring Diagram

    Lynx Figure 16a. Schematic wiring diagram.
  • Page 21: Boiler Control

    Lynx BOILER CONTROL SPARK IGNITOR SPARK CABLE GROUND FUSE USED USED ARGUS VISION CONTROL Figure 16b. Boiler Control. NEUTRAL 120V/60HZ DISCONNECT SWITCH BOILER ON/OFF SWITCH BOILER CIRCULATOR DHW CIRCULATOR (IF USED) 120V SECTION OF WATER HIGH CONTROL BOARD LIMIT VALVE 120V SPARK 120V...
  • Page 22: Single And Multi Zoning

    Lynx MULTIZONING OF "LYNX" BOILER; ZONE VALVE SYSTEM USING V8043E/F ZONE VALVES AND R845A RELAY ZONE 2 ZONE 3 ZONE 1 DISCONNECT THERMOSTAT THERMOSTAT THERMOSTAT SWITCH V8043E/F V8043E/F V8043E/F 120V/24V POWER SUPPLY, PROVIDE DISCONNECT TRANSFORMER MEANS AND OVERLOAD PROTECTION TH-TR SWITCH MOTOR SWITCH...
  • Page 23 Lynx MULTIZONING OF "LYNX" BOILER; PUMP ZONING SYSTEM USING R882A/B RELAYS ZONE 3 THERMOSTAT ZONE 2 ZONE 1 THERMOSTAT THERMOSTAT DISCONNECT SWITCH R882A/B R882A/B R882A/B 120V/60HZ 120V/24V TRANSFORMER CIRC. CIRC. CIRC. ZONE 2 ZONE 1 ZONE 3 POWER SUPPLY, PROVIDE DISCONNECT FIELD WIRING 1 2 3 4 5 6 7 8 MEANS AND OVERLOAD PROTECTION...
  • Page 24: Water Piping

    Any use of anti-freeze other than that supplied by 22. An air vent is recommended to be installed on an air Slant/Fin or approved will void the warranty. separator in close proximity to the expansion tank. E. Cold Water Fill:...
  • Page 25 Lynx Figure 18. Relief Valve and Low Water Cutoff Installation...
  • Page 26 Lynx Head (feet w.c.) Flow Rate (GPM) Figure 19. Boiler water side pressure drop Available Head Capability Left for Various Domestic Boiler Boiler Flow Temp Water Model Circulators to Overcome DHW Tank Head Model Rate Rise Tank Piping Head Loss (Feet w.c.) *** Loss Head Loss ** (gpm)
  • Page 27 Lynx Figure 20. Zoning with circulators.
  • Page 28 Lynx Figure 21. Zoning with zone valves.
  • Page 29 Lynx Figure 22. Piping a heating-cooling system to the boiler and a chiller.
  • Page 30: Operating Instructions

    Lynx OPERATING INSTRUCTIONS 3. While “t” is blinking, DHW tank temperature may be set to desired temperature (if tank is equipped with I. FILLING AND VENTING WATER SYSTEMS sensor). The setting range is between 104˚ to 185˚F. 4. View actual boiler supply & return water tempera- A.
  • Page 31: Boiler Operating Status

    Lynx "TEMPERATURE" DISPLAY (3 DIGITS) "MODE" DISPLAY "UP" PUSH BUTTON "DOWN" PUSH BUTTON "RESET" PUSH BUTTON "ENTER" PUSH BUTTON "BURNER STATUS" "SELECT" PUSH BUTTON STEADY DOT = BURNER ON BLINKING DOT = BURNER OFF Figure 23. Display Board Table 3 LYNX BOILER DISPLAY BOARD “Boiler Operation Status”...
  • Page 32: Viewing And Changing Temperature

    Lynx Table 4 VIEWING AND CHANGING TEMPERATURES Press “SELECT” button for viewing different modes on “MODE DISPLAY” MODE DESCRIPTION & TEMPERATURE DISPLAY DISPLAY Space heating supply water temperature could be changed by pressing “Up/Down” button. Settable from 90˚F to 185˚F (steps of 1 F).
  • Page 33: Viewing And Changing System Setting

    3: Space heating priority for limited time Changing priority limited time. Settable from 20 to 80 minutes. The default value is 30 minutes. Boiler model selection, values are: for model LX-90 for model LX-120 for model LX-150 Boiler model confirmation, values are:...
  • Page 34 Lynx Maximum water target temp. 185 ° F Water Supply Target Temp. (° F) Minimum water target temp. Water reference temp. (default of 86°F) 68°F Outdoor Temp. (°F) Figure 24. Space Heating mode with outside sensor water set point graph.
  • Page 35: Initial Start And Operating Instruction

    Lynx III. INITIAL START C. Use only your hand to turn the gas supply shut-off valve. Never use tools. If the supply shut-off valve will not turn by Safe lighting and other performance criteria were met when testing hand, don’t try to repair it, call a qualified service technician. various gas manifold and control assemblies used on the Lynx Force or attempted repair may result in a fire or explosion.
  • Page 36: Sequence Of Operation

    Lynx LYNX BOILER SEQUENCE OF OPERATION THERMOSTAT CALLS FOR HEAT CIRCULATOR(S) ON COMBUSTION BLOWER ON (AT MEDIUM SPEED) CONTROL LOCKOUT BLOWER SPEED CONFIRMED? DISPLAY SHOWS ERROR “A 33” 5 SECOND PRE-PURGE PERIOD CONTROL LOCKOUT DISPLAY SHOWS ERROR “A 01” CONTROL LOCKOUT WATER HIGH LIMIT DISPLAY SHOWS CLOSED?
  • Page 37: Combustion Check And Fuel Input Rate

    E. If the combustion (CO2 and CO measurement) at either high or low input rate is out of the range, shut down the boiler and contact Slant/Fin Tech. service department at 1-800-873-4346. Warning: Failure to comply with the above mentioned requirement might result in property damage, personal injury or loss of life.
  • Page 38: Diagnostic Error Codes

    Lynx VI. DIAGNOSTIC ERROR CODES WARNING: Only a trained, experienced service technician should perform troubleshooting. Turn off all electric power to the boiler before service. A. LOCKOUT ERRORS: Indicated by an “A” in the mode display. The reset button must be pressed to clear the error and retry operation.
  • Page 39 Lynx B. BLOCKING ERRORS: Indicated by an “E” in the mode display. Operation is automatically restored, once the condition returns to normal or is fixed. The temperature display shows the error code. Pressing the “Reset” button is not required. ERROR CODE INDICATION REMEDY Check wire harness connections going to the...
  • Page 40 Lynx continued from page 39 ERROR CODE INDICATION REMEDY Check flue gas temperature, at the maximum firing rate and high water temperature. If the flue gas temperature reaches 212˚F, check the fuel input Excess Flue Temperature rate and combustion. Check the condition of the heat exchanger.
  • Page 41: Care And Maintenance

    Inspection”, see page 18. water passage blockage, service to remedy situation must be C. Piping performed only by an authorized Slant/FIn representative. Check the following: B. Burner: In the unlikely event of blockage or deterioration, 1. Water piping and accessories for leaks. Slightest leaks should be corrected.
  • Page 42: General Troubleshooting Guide

    Lynx GENERAL TROUBLESHOOTING GUIDE FOR SERVICE PERSONNEL WARNING: Only a trained, experienced service technician should perform troubleshooting. Turn off all electrical power to the boiler before servicing. A. BURNER FAILS TO OPERATE - NO HEAT CAUSE REMEDY 1. No power, display off, power switch off. Main electric 1.
  • Page 43 Lynx NOTES:...
  • Page 44 ©Slant/Fin Corp. 2013. SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600 FAX: (516) 484-5921 • Canada: Slant/Fin , Mississauga, Ontario LTD/LTEE www.slantfin.com...