Setup At Local Site And Others; Various Setting On Outdoor Unit - Toshiba Carrier RAV-SP180AT2-UL Service Manual

Ac split type outdoor unit super digital inverter
Hide thumbs Also See for Carrier RAV-SP180AT2-UL:
Table of Contents

Advertisement

10-1. Outdoor Unit
10-1-1. Various Setting on Outdoor Unit (Power save, Cooling-only, etc.)
The following settings are available by DIP switch setup and jumper line setup.
<RAV-SP180AT2-UL>
Function
Power save
setup
Power saving setting
Cooling only setting
Cooling-only
setup
<RAV-SP240, SP300, SP360, SP420AT2-UL>
Function
High static
pressure
SW802
setup
Power save
setup
∗ all are OFF at shipment.
Snow-proof
fan control
Defrost
time change
Max.
frequency
change
Cooling-only
setup

10. SETUP AT LOCAL SITE AND OTHERS

Set position
SW802
Set position
High static pressure setup
Power save setup
Snow-proof fan control
J805, J806
J807
J808
Control contents
When using the power saving function, turn on switches.
The maximum operating current of the COOL/HEAT operation can
be limited by dropping the current release point of the outdoor unit.
When using the outdoor unit as a cooling-only machine, turn on
switches. ("OF" of DN cord on the remote controller also can be
used for changing the machine to the cooling-only model.)
Control contents
Turn the switch to ON when mounting a duct to the discharge port
of the outdoor unit.
Add 3 taps to the upper limit value of the outdoor fan tap.
The operation is performed with
(Max: Upper fan: 890 rpm / Lower fan: 910 rpm (WF)).
In this case, the upper limit value of static pressure for duct is 5Pa
or less on 77°F (25°C) degrees and please use straight duct.
In this case, the outdoor noise level may increase.
Turn the switch to ON when using the power save function.
The control to lower the compressor frequency (Approx. –10%) is
performed by indoor heat exchanger temp. in heating operation.
When snow enters from clearance of the fan guard or heat
exchanger into blast path and it is accumulated, the control to
prevent generation of motor lock is validated.
When outside temp. is below 32°F (0°C) though the compressor
stops, the outdoor fan operates with W5.
The defrost interval is cut to shorten it than the standard status.
For contents of control and cutting method, refer to
10. Defrost control (See to Page 43).
When it is needed to lower the maximum value of the compressor
frequency, cut the jumper line. Max. frequency at cooling/heating is
lowered.
In this case the Max. capacity decreases.
Max. frequency of compressor
SP240
RAV-
Model
COOL
Standard status
72.0
When J807 is cut
72.0
When using the air conditioner as a cooling-only conditioner, cut
the jumper line. (An air conditioner can be changed to cooling-only
conditioner by "0F" of DN code on the remote controller.)
– 75 –
Revised : Feb. 2010
SP300
SP360, SP420
HEAT
COOL
HEAT
COOL
99.6
53.4
71.4
64.2
79.2
53.4
64.2
64.2
HEAT
90.6
72.0