Toshiba Carrier RAV-SP180AT2-UL Service Manual page 54

Ac split type outdoor unit super digital inverter
Hide thumbs Also See for Carrier RAV-SP180AT2-UL:
Table of Contents

Advertisement

Operation of diagnostic function
Check code
Indoor unit
Cause of operation
4-Way
Under
High
Ceiling
Wall
Discharge temp. error
P03
P03
∗ Discharge temp. (TD) over
specified value was detected.
P04
Case thermostat operation
H04
∗ Abnormal overheat of compressor
P04
High-pressure SW error
P05
Power supply voltage error
High pressure protective operation
• During cooling operation, outdoor
temp. sensor (TL) detected
P20
temperature over specified temp.
• During heating operation, indoor
temp. sensor (TC, TCJ) detected
temperature over specified temp.
P22
P22
Outdoor fan system error
Short-circuit error of compressor
P26
P26
driving element
P29
P29
Position detection circuit error
Status of
Condition
air conditioner
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Stop
Displayed when
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
– 54 –
Judgment and measures
1. Check refrigerating cycle (Gas leak)
2. Trouble of electronic expansion valve
3. Check discharge temp. sensor (TD).
1. Check case thermostat and connector.
2. Check gas leak, recharge
3. Check full open of service valve.
4. Check PMV (Pulse Motor Valve).
5. Check broken pipe.
• Check full-open of service valve.
• Check outdoor fan error.
• Check outdoor fan motor error.
• Check clogging of outdoor PMV.
• Check loading of indoor/outdoor heat exchangers.
• Short-circuit of outdoor discharge/suction air
• Check outdoor P.C. board (I/F) error.
• Check error of fan system (air volume drop) at indoor side.
• Check miswiring of communication line between indoor and
outdoor.
• Check overcharge of refrigerant.
1. Check power supply voltage. AC198 to 253V
1. Check outdoor heat exchanger sensor (TL).
2. Check indoor heat exchanger sensor (TC, TCJ).
3. Check full open of service valve.
4. Check indoor/outdoor fan.
5. Check PMV (Pulse Motor Valve).
6. Check clogging and short circuit of indoor/outdoor heat
exchanger.
7. Overcharge of refrigerant. Recharge
1. Check lock of fan motor.
2. Check power supply voltage. AC198 to 253V
3. Check outdoor P.C. board.
1. When performing operation while taking-off compressor
wire, P26 error occurs. Check control P.C. board.
2. When performing operation while taking-off compressor
wire, an error does not occur. (Compressor rare short)
1. Check control P.C. board.