CODE
Outdoor
No.
LED display
[F08]
<Display 1> <Display 2>
[F12]
<Display 1> <Display 2>
[F13]
<Display 1> <Display 2>
[F15]
<Display 1> <Display 2>
[F31]
<Display 1> <Display 2>
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[Outside air temp. sensor (TO) error]
Is CN602 connection normal?
Is resistance value of TO sensor normal?
YES
Check outdoor P.C. board.
Defect → Replace
[Suction temp. sensor (TS) error]
Is CN600 connection normal?
Is resistance value of TS sensor normal?
YES
Check outdoor P.C. board.
Defect → Replace
[Heat sink temp. sensor (TH) error]
Check outdoor P.C. board.
Defect → Replac
[Miswiring of heat exchanger sensor (TE, TS)]
Is mounting status of
TE and TS sensors normal?
YES
Is CN600 connection normal?
Is resistance value of TS sensor normal?
YES
Is CN601 connection normal?
Is resistance value of TE sensor normal?
YES
Check outdoor P.C. board.
Defect → Replace
[EEPROM error]
Check outdoor P.C. board.
Defect → Replace
– 62 –
NO
Correct connector.
Sensor error → Replace
NO
Correct connector.
Sensor error → Replace
NO
Correct sensor mounting.
NO
Correct connector.
Sensor error → Replace
NO
Correct connector.
Sensor error → Replace