Toshiba Carrier RAV-SP180AT2-UL Service Manual page 73

Ac split type outdoor unit super digital inverter
Hide thumbs Also See for Carrier RAV-SP180AT2-UL:
Table of Contents

Advertisement

8-2-5. Outdoor Unit
No.
Part name
Compressor
(Model :DA111A1FD-21F)
1
Compressor
(Model :DA220A2-22L)
2
Compressor
(Model :DA422A3F-25M)
3
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
– 73 –
Revised : Feb. 2010
Checking procedure
Position
Red – White
White – Black
Black – Red
Position
Red – White
White – Black
Black – Red
Position
Red – White
White – Black
Black – Red
Resistance value
1.07 Ω
Under 20°C
Resistance value
0.606 Ω
Under 20°C
Resistance value
0.264 Ω
Under 20°C