Baxi Combi 130 HE Installation And Servicing Instructions page 15

Gas fired wall mounted condensing combination boiler
Table of Contents

Advertisement

Fig. 11
1m
0.5m
Pictorial examples of flue runs where EQUIVALENT flue length equals 4m
Supplied By www.heating spares.co Tel. 0161 620 6677
1m
Fig. 13
7.0 Site Requirements
7.9
Flue Dimensions
See Section 1.2. The standard horizontal flue kit
allows for flue lengths between 270mm and
800mm from elbow to terminal (Fig. 11).
The maximum permissible equivalent flue
length is: 4 metres horizontal (Fig. 12).
NOTE: Each additional 45° of flue bend will
account for an equivalent flue length of 0.5m.
eg. 45° = 0.5m,
7.10
Terminal Guard (Fig. 13)
1. When codes of practice dictate the use of
terminal guards, they can be obtained from most
Plumbers' and Builders' Merchants.
2. There must be a clearance of at least 50mm
between any part of the terminal and the guard.
0.5m
3. When ordering a terminal guard, quote the
appliance name and model number.
Fig. 12
4. The flue terminal guard should be positioned
centrally over the terminal and fixed as
illustrated.
90° = 2 x 45° = 1m etc.
15

Hide quick links:

Advertisement

Table of Contents