Termination Clearances; Venting Requirements - Natural Vent Only; Venting Runs - Vermont Castings OXDV30NVSB Installation And Operating Instructions Manual

Vermont castings direct vent gas stove
Table of Contents

Advertisement

Oxford Direct Vent / Natural Vent Gas Heater

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
G =
Combustible
G
6" (152 mm)
Noncombustible
V
2" (51 mm)
Balcony -
with no side wall
M
V
M =
Combustible &
Noncombustible
12" (305 mm)
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3' (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10' (1 m) of a termination cap must be a minimum of 3' (914 mm) below the termination cap. 3. All
gravity air intakes within 3' (914 mm) of a termination cap must be a minimum of 1' (305 mm) below the termination cap.
Fig. 10 Termination clearances.
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
1 2 4 6 8 10 12 14 16 18 20 22 24
Fig. 11 Vent termination window - Natural Vent ONLY.
12
Outside Corner
V
F
Balcony -
with perpendicular side wall
M
Combustible &
Noncombustible
M = 24" (610 mm)
P = 20" (508 mm)

Venting Requirements - Natural Vent Only

A
B
Horizontal Run (in feet)
Alcove Applications*
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
of Caps
V
P
D
Min.
C
Max.

Venting Runs

NOTE: When venting staight vertical, without any
elbow, a minimum of 8 ft. vertical is required
off the top of the stove.
= Acceptable venting configuration
= Unacceptable venting configuration
A: Vertical installations up to 36 feet (12m) in
height. Up to an 18 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 90-degree elbows or four
45-degree elbows.
B: Vertical installations up to 36 feet (12m) in
height. Up to a 24 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 45-degree elbows.
(Ratio = 2/3, Hor./Vert.)
NOTE: When using the FSDHAG, the restrictor
plate supplied with the stove is not used.
FP567
NVBR/NVBC VENTING RUNS
11/12/97
D
C
C
V
E
O
E
= Min. 6" (152 mm) for
non-vinyl sidewalls
Min. 12" (305 mm) for
vinyl sidewalls
O
= 8' (2.4 m) Min.
No.
D
C
Min.
1
3' (914 mm) 2 x D
2
6' (1.8 m)
1 x D
3
9' (2.7 m)
2/3 x D
4
12' (3.7 m)
1/2 x D
= # of Termination caps x 3
= (2 / # termination caps) x D
Actual
Max.
Actual
Actual
Actual
Actual
584-15