Nordyne S3BM-120G User's Information And Installation Instructions Manual page 9

High efficiency commercial split system
Table of Contents

Advertisement

PHYSICAL AND ELECTRICAL SPECIFICATIONS / OUTDOOR UNITS
9 E.E.R. - High Effi ciency (380 Volt) - Three Phase (50Hz)
Gross Cooling Capacity
NET Cooling Capacity
Performance Data
Rated Airfl ow (CFM)
Effi ciency-E.E.R. (Btu/Watt)
Volts-Phase-Hz
Voltage Range (Min-Max)
Total Amps
Electrical Data
Min. Circuit Ampacity
Delay Fuse max. (1)
Wire Size/Max Length (AWG 60° C Cu)
Wire Size/Max Length (AWG 75° C Cu)
Coil
Fan Motor
Component Data
Fan Blade
Compressor Data
Refrigerant Suction Line-Length/O.D.
(Liquid Line all lengths - 5/8" O.D.)
Circuits (Qty) -1
Refrigerant Charge
Holding
Total System with
R-22 Ounces
25' Lineset (2)
Weight Approximate (lbs.)
Net capacity includes indoor blower motor heat deduction.
Gross capacity does not include indoor blower motor heat deduction.
(1) HACR Type circuit breakers may be used.
(2) Add 9.0 oz. of refrigerant per 5ft. of additional lineset.
(3) Requires 1-3/8" to 1-1/8" reducer from unit to line.
Table 2. S3BM-120G Electrical Specifi cations
Area
Rows-FPI
Tube Diameter
Volts-Phase-Hz
Qty
Horsepower
Full Load LRA
Diameter/Pitch/# Blades
RPM/CFM (Max-Total)
Voltage-Phase-Hz
Qty/Type
Model
RLA
LRA
Stages/Percent
Crankcase Heater Qty./Type
0 - 15 ft.
16 - 25 ft.
26 - 75 ft.
Net:
Ship:
NOTES:
122,500
117,000
3,600
9.00
380-420/3/50
360-440
20.1
24.5
40
10
10
31.94
1-22
3/8 O.D.
380-420/3/50
1
1
2.4
30-19-3
900/8,000
380-420/3/50
1/Scroll
ZR144KC
17.7
118
1/100
1/Band
1 1/8"
1 1/8"
1 3/8" (3)
76
392
341
378
9