S5BD SERIES 13 SEER USER’S MANUAL / INSTALLATION INSTRUCTIONS SPLIT SYSTEM AIR CONDITIONER - R-22 IMPORTANT Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future.
USER INFORMATION WARRANTY INFORMATION Important Safety Information ........3 Operating Instructions ..........3 A warranty certificate with full details is included with the Cooling Operation .............3 air conditioner. Carefully review these responsibilities with Heating Operation .............3 your dealer or service company. The manufacturer will not Operating the Air Conditioner for Automatic be responsible for any costs found necessary to correct Cooling and Heating ..........3...
USER INFORMATION IMPORTANT SAFETY INFORMATION The continuous indoor blower operation can be obtained with the thermostat system mode set in any position, Safety markings are used frequently throughout this including OFF. manual to designate a degree or level of seriousness and should not be ignored.
INSTALLER INFORMATION IMPORTANT SAFETY INFORMATION CAUTION: INSTALLER: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and This unit uses R-22 refrigerant. DO NOT use any other special notes highlighted in the manual. Safety any other refrigerant in this unit. Use of another markings are used frequently throughout this manual to refrigerant will damage the unit.
AIR CONDITIONER INSTALLATION Packaging Removal NOTE: To prevent damage to the tubing connections, General Information carefully remove the carton and user’s manual from the Split system air conditioners are designed only for outdoor equipment. Discard the shipping carton. rooftop or ground level installations. This unit has been tested for capacity and efficiency in accordance with Ground Level AHRI Standards and will provide many years of safe...
• To maintain the unit's warranty, it is required that a Connecting Refrigerant Tubing Between the Indoor & Outdoor Unit filter drier be installed when the system is open to the atmosphere. This includes, but is not limited to, CAUTION: replacing the evaporator and/or condenser of a system.
on the outdoor unit data label. Any other wiring methods Thermostat Connections • Thermostat connections should be made in accordance must be acceptable to authority having jurisdiction. • The outdoor unit requires both power and control circuit with the instructions supplied with the thermostat and the indoor equipment.
• Refrigerant charging charts are applicable only to as necessary. matched assemblies of NORDYNE equipment and 3. Verify HI and LO refrigerant pressures. listed airflows for the indoor coil. Refer to Figures 3 - 9 4.
The ability to properly REPLACEMENT PARTS perform maintenance on this equipment requires certain Replacement parts are available through all Nordyne distributors. mechanical skills and tools. If you do not possess these Please have the complete model and serial number of the unit skills, contact your dealer for maintenance.
FIGURES & TABLES DO NOT OBSTRUCT TOP OF UNIT Allow adequate clearance for airflow Model Number S5BD- Height -H- Width -W- Depth -D- 23" 22 3/4" 22 3/4" 018KA 23" 22 3/4" 22 3/4" 024KB 27" 22 3/4" 22 3/4" 030KB 27"...
Page 11
S5BD-024KB SERIES CHARGING CHART Remove refrigerant when above curve Add refrigerant when below curve Liquid Temperature (F) Figure 4. Charging Chart for 2 Ton Units (with Microchannel Coil) S5BD-030KB SERIES CHARGING CHART Remove refrigerant when above curve Add refrigerant when below curve Liquid Temperature (F) Figure 5.
Page 12
S5BD-036KB SERIES CHARGING CHART Remove refrigerant when above curve Add refrigerant when below curve Liquid Temperature (F) Figure 6. Charging Chart for 3 Ton Units (with Microchannel Coil) S5BD-042KA SERIES CHARGING CHART Remove refrigerant when above curve Add refrigerant when below curve Liquid Temperature (F) Figure 7.
Page 13
S5BD-048KA SERIES CHARGING CHART Remove refrigerant when above curve Add refrigerant when below curve Liquid Temperature (F) Figure 8. Charging Chart for 4 Ton Units S5BD-060KA SERIES CHARGING CHART Remove refrigerant when above curve Add refrigerant when below curve Liquid Temperature (F) Figure 9.
FIGURES & TABLES REFRIGERANT CHARGING TABLES Shaded boxes indicate flooded conditions. Rated design values. The suction pressure will vary from design value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design. 1. All pressures are listed in psig and all temperatures in ° F 2.
Page 15
REFRIGERANT CHARGING TABLES Shaded boxes indicate flooded conditions. Rated design values. The suction pressure will vary from design value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design. 1. All pressures are listed in psig and all temperatures in ° F 2.
Page 16
REFRIGERANT CHARGING TABLES Shaded boxes indicate flooded conditions. Rated design values. The suction pressure will vary from design value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design. 1. All pressures are listed in psig and all temperatures in ° F 2.
OUTDOOR TEMPERATURE (° F) Suct. Press. Liq. Dis. Liq. Dis. Liq. Dis. Liq. Dis. Liq. Dis. Liq. Dis. Liq. Dis. Liq. Dis. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp. Table 10. Charging Table for S5BD-060KA Series (5 Ton Units) ELECTRICAL INFORMATION Model Number S5BD- 018KA...
Page 18
WIRING DIAGRAM Split System Air Conditioner (Outdoor Section) Single Phase NOTES: Optional Hard Start Kit 1. Couper le courant avant de faire letretien. 1. Disconnect all power before servicing. 2. Employez uniquement des conducteurs 2. For supply connections use copper conductors only. to “H”...
Page 20
Specifications & illustrations subject to change without notice or incurring obligations. O’ Fallon, MO | Printed in U.S.A. (01/13) 7095990 (Replaces 7093790)