Outdoor Heat Pump User’s Information and Installation Instructions T3BN Series High Effi ciency Commercial Split System These units have been designed and tested for capacity and effi ciency in accor- dance with A.R.I. Standards. Split System Heat Pump units, when combined with our air handlers, offer a high quality, matched heating and cooling system.
OPERATING INSTRUCTIONS 2. Set the thermostat temperature to the desired temperature level using the temperature selector. Please refer to TO OPERATE YOUR HEAT PUMP the separate detailed thermostat user’s manual for complete instructions regarding FOR COOLING — thermostat programming. The outdoor unit 1.
Page 3
normal, and the unit will periodically defrost TO MAINTAIN YOUR HEAT PUMP— itself. During the defrost cycle, the outdoor fan will stop, and the compressor will continue CAUTION: to run and heat the outdoor coil, causing the snow and ice to melt. After the snow and ice have melted, some steam may rise from the Be certain the electrical power to outdoor unit as the warm coil causes some...
Read Your Warranty the instructions provided with the equipment prior to performing the installation and operational Please read the separate warranty document checkout of the equipment. completely. It contains valuable information about your system. Brazing Operations — Installation of equipment may require brazing operations.
INSTALLING THE OUTDOOR UNIT The maximum recommended interconnecting refrigerant line length is 75 feet, and the vertical elevation difference between the indoor Slab Mount — The site selected for a slab mount and outdoor sections should not exceed 20 installation requires a stable foundation and one feet.
Electrical Power Wiring — Electrical power Optional Equipment (e.g.: liquid line solenoid wiring must comply with the current provisions valves, refrigerant compressor crankcase heater, of the “National Electrical Code” (ANSI/NFPA etc.) should be installed in strict accordance with 70) and with applicable local codes having the manufacturer’s installation instructions.
Thermostat G R W 2 C E O Y NOTE: Jumper between W2 and E is required when no OD T-Stat is used. C & W2 to be connected to Electric Heat. Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler...
Page 8
Indoor Blower — Set the thermostat function indoor blower have energized. Feel the air being switch to COOLING and the fan switch to ON. circulated by the indoor blower and verify that Verify that the indoor blower is operating and it is warmer than ambient temperature.
Page 9
2. Jumper the “T2”-”DFT” test pins. This will Speed up changes: indicate to the board that the defrost T-stat Manually initiating a defrost will cause the is closed(if the compressor is running). compressor to run continually when entering Defrost T-stat is closed at 32° or below and defrost.
PHYSICAL AND ELECTRICAL SPECIFICATIONS / OUTDOOR UNITS 10.1 EER —High Effi ciency — Three Phase Model No. T3BN- 090C 090W 120C 120W 280/230-3-60 460-3-60 280/230-3-60 460-3-60 Volts-Phase-Hz 380/420-3-50 380/420-3-50 Voltage Range (Min-Max) 187-253 414-506 187-253 414-506 Total Amps 32.1 16.4 33.4 17.2 Electrical Data...
Page 16