Gas Piping; Gas Connection; External Supply Connection External Shut-Off; Natural Gas Pipe Sizing Chart - York DNZ 024 Installation Manual

Single package gas/electric air-cooled air conditioners 2, 2-1/2, 3, 3-1/2, 4 and 5 nominal ton with r-410a refrigerant
Table of Contents

Advertisement

GAS PIPING

Proper sizing of gas piping depends on the cubic feet per
hour of gas flow required, specific gravity of the gas and the
length of run. National Fuel Gas Code Z223.1 or CSA B149.1
should be followed in all cases unless superseded by local
codes or gas company requirements. Refer to Tables 5 & 6.
The heating value of the gas may differ with locality. The
value should be checked with the local gas utility.
NOTE: There may be a local gas utility requirement specify-
ing a minimum diameter for gas piping. All units
require a 1/2 inch pipe connection at the gas valve.

GAS CONNECTION

The gas supply line can be routed through the hole located
on the left side of the unit. Refer to Figure 6 to locate these
access openings. Typical supply piping arrangements are
shown in Figure 4.
Gas piping requirements:
1.
A drip leg and a ground joint union must be installed in
the gas piping.
2.
When required by local codes, a manual shut-off valve
may have to be installed outside of the unit.
3.
Use wrought iron or steel pipe for all gas lines. Pipe dope
should be applied sparingly to male threads only.
1 / 2 x 1 / 2 U N I O N
1 / 2 x 1 / 2 G A S C O C K
D R I P L E G
FIGURE 4 - EXTERNAL SUPPLY CONNECTION
EXTERNAL SHUT-OFF
10
A U T O M A T I C
G A S V A L V E
1 / 2 - 1 4 N P T
TABLE 5: NATURAL GAS PIPE SIZING CHART
NOMINAL INCHES IRON PIPE SIZE
LENGTH
IN FEET
1/2"
10
132
20
92
30
73
40
63
50
56
60
50
70
46
80
43
90
40
100
38
1.
Maximum capacity of pipe in cubic feet of gas per hour
(based upon a pressure drop of 0.3 inch water column
and 0.6 specific gravity gas).
TABLE 6: PROPANE (LP) GAS PIPE SIZING
1
CHART
NOMINAL INCHES IRON PIPE SIZE
LENGTH
IN FEET
1/2"
10
275
20
189
30
152
40
129
50
114
60
103
70
96
80
89
90
83
100
78
1.
Maximum capacity of pipe in thousands of BTU per
hour (based upon a pressure drop of 0.5 inch water col-
umn).
66433-YIM-B-1004
3/4"
1"
1-1/4"
278
520
1,050
190
350
730
152
285
590
130
245
500
115
215
440
105
195
400
96
180
370
90
170
350
84
160
320
79
150
305
3/4"
1"
1-1/4"
567
1,071
2,205
393
732
1,496
315
590
1,212
267
504
1,039
237
448
913
217
409
834
196
378
771
185
346
724
173
322
677
162
307
630
Unitary Products Group