TECHNICAL GUIDE
AFFINITY™ SERIES
SINGLE PACKAGE GAS/ELECTRIC
AIR COOLED AIR CONDITIONERS
2 THRU 5 NOMINAL TON
DNP024, 030, 036, 042, 048 AND 060
13 SEER
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

DESCRIPTION

®
York
Affinity™ Series packaged cooling/heating air condi-
tioners are designed for outdoor installation. Only utility and
duct connections are required at the point of installation.
The gas-fired heaters have aluminized steel tubular heat
exchangers and hot surface to pilot ignition. They are avail-
able in natural gas with field conversion to propane.
FEATURING
FACTORY MOUNTED TXV
COOLING/GAS HEATING UNITS (NATURAL GAS OR
PROPANE)
LOW PROFILE
QUIET OPERATION
COMMON FOOTPRINT
OPTIONAL SLIDE IN MOTORIZED DAMPERS
OPTIONAL SLIDE IN ECONOMIZERS
OPTIONAL PROPANE CONVERSION KIT
OPTIONAL HIGH ALTITUDE CONVERSION KIT
(NATURAL GAS/PROPANE)
OPTIONAL LOW NOx KIT
FULL PERIMETER BASE RAILS
BOTTOM AND SIDE UTILITY CONNECTIONS
1" OR 2" CLEANABLE FILTERS STANDARD ON ALL
3 PHASE MODELS. OPTIONAL ON 1 PHASE MODELS
WARRANTY - 1 PHASE
10 year compressor
20 year heat exchanger
5 year other parts
WARRANTY - 3 PHASE
5 year compressor
10 year heat exchanger
1 year other parts
036-21366-007-A-1205

Advertisement

Table of Contents
loading

Summary of Contents for York DNP024

  • Page 1: Description

    TECHNICAL GUIDE AFFINITY™ SERIES SINGLE PACKAGE GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 2 THRU 5 NOMINAL TON DNP024, 030, 036, 042, 048 AND 060 13 SEER FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE DESCRIPTION ®...
  • Page 2: Table Of Contents

    RATINGS COOLING/GAS HEATING ... . . 7 DNP024 COOLING CAPACITIES - 2 TON ..8 DNP030 COOLING CAPACITIES - 2-1/2 TON ..10 DNP036 COOLING CAPACITIES - 3 TON .
  • Page 3: Standard Features/Benefits

    036-21366-007-A-1205 STANDARD FEATURES/BENEFITS OPERATING EFFICIENCY - All units provide high operating efficiencies and have a minimum AFUE of 80% and SEER of 13.0. All efficiencies exceed legislated minimum levels. ON SITE FLEXIBILITY - All model sizes share a common, compact design cabinet in a single footprint. The installer has the flexibility of setting one curb and placing the proper ton- nage unit on that curb after the internal load has been deter- mined.
  • Page 4: Field-Installed Accessories

    FAN SYSTEM - All 2-1/2, 3, 3-1/2 and 4 ton models operate over a wide range of design conditions with a constant CFM, electrically commutated (ECM) fan motor. These units easily match all types of applications and provide greater on site flexibility to match comfort requirement.
  • Page 5 036-21366-007-A-1205 enthalpy to determine the most economical mix. Single Enthalpy sensor also required. PRESSURE SWITCH UPGRADE KIT - Contains screw in type High pressure, Low Pressure/Loss of Charge switch, freeze protection switch and lockout relay. Switches are placed onto existing scharder ports located in the unit by fur- nished adapters.
  • Page 6: Unit Component Location

    BLOW-THROUGH DESIGN WITH RELIABLE ALUMINIZED STEEL TUBULAR HEAT EX HANGERS LONG LASTING POWDER PAINT FINISH REAR AND BOTTOM RET R U N AIR AND SUPPLY AIR DUCT OPENINGS HEAVY GAUGE REMOVABLE BASE RAILS BLOWER MOTOR WITH SLIDE-OUT BLOWER ASSEMBLY FIGURE 2 - UNIT COMPONENT LOCATION TABLE 1: PHYSICAL DATA MODEL CENTRIFUGAL BLOWER (Dia.
  • Page 7: Ratings Cooling/Gas Heating

    036-21366-007-A-1205 TABLE 2: RATINGS COOLING/GAS HEATING NET COOLING CAPACITY MODEL SEER 024N03606 25.4 13.3 024N05606 25.4 13.3 030N03606 30.6 13.4 030N03625 30.6 13.4 030N03646 30.6 13.4 030N05606 30.6 13.4 030N05625 30.6 13.4 030N05646 30.6 13.4 036N03606 37.4 13.65 036N03625 37.4 13.65 036N03646 37.4...
  • Page 8: Dnp024 Cooling Capacities - 2 Ton

    TABLE 3: DNP024 COOLING CAPACITIES - 2 TON TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL POWER CAP. INPUT °F 24.7 1.90 15.0 22.6 1.91 18.4 20.9 1.89 20.9 20.6 1.88 20.6 26.4 1.94 17.0 24.1 1.94 20.7 22.3...
  • Page 9 036-21366-007-A-1205 TABLE 3: DNP024 COOLING CAPACITIES - 2 TON (CONT’D) AIR ON EVAPORATOR COIL CAP. °F 18.4 16.6 16.2 16.5 19.3 17.4 17.0 17.2 20.1 18.1 17.7 18.0 20.4 18.3 17.9 18.2 20.6 18.5 1000 18.1 18.4 These capacities are net capacities (the indoor fan heat is deducted).
  • Page 10: Dnp030 Cooling Capacities - 2-1/2 Ton

    TABLE 4: DNP030 COOLING CAPACITIES - 2-1/2 TON TEMPERATURE OF AIR ON CONDENSER COIL NET CAP.MBH TOTAL POWER INPUT kW 85 °F NET CAP. MBH TOTAL POWER INPUT kW 95 °F NET CAP.MBH TOTAL POWERINPUT kW 105 °F NET CAP.MBH TOTAL POWER NPUT kW 115 °F NET CAP.
  • Page 11: Dnp036 Cooling Capacities - 3 Ton

    036-21366-007-A-1205 TABLE 5: DNP036 COOLING CAPACITIES - 3 TON TEMPERATURE OF AIR ON CONDENSER COIL NET CAP. TOTAL POWER INPUT kW 85 °F NET CAP. TOTAL POWER INPUT kW 95 °F NET CAP. TOTAL POWER INPUT kW 105 °F NET CAP. TOTAL POWER INPUT kW 115 °F...
  • Page 12: Dnp042 Cooling Capacities - 3-1/2 Ton

    TABLE 6: DNP042 COOLING CAPACITIES - 3-1/2 TON TEMPERATURE OF AIR ON CONDENSER COIL NET CAP. TOTAL POWER 85 °F NET CAP. TOTAL POWER 95 °F NET CAP. TOTAL POWER 105 °F NET CAP. TOTAL POWER 115 °F NET CAP. TOTAL POWER 125 °F These capacities are net capacities (the indoor fan heat is deducted)
  • Page 13: Dnp048 Cooling Capacities - 4 Ton

    036-21366-007-A-1205 TABLE 7: DNP048 COOLING CAPACITIES - 4 TON TEMPERATURE OF AIR ON CONDENSER COIL NET CAP. TOTAL POWER INPUT kW 85 °F NET CAP. TOTAL POWER INPUT kW 95 °F NET CAP. TOTAL POWER INPUT kW 105 °F NET CAP. TOTAL POWER INPUT kW 115 °F...
  • Page 14: Dnp060 Cooling Capacities - 5 Ton

    TABLE 8: DNP060 COOLING CAPACITIES - 5 TON TEMPERATURE OF AIR ON CONDENSER COIL NET CAP. TOTAL POWER INPUT kW 85 °F NET CAP. TOTAL POWER INPUT kW 95 °F NET CAP. TOTAL POWER INPUT kW 105 °F NET CAP. TOTAL POWER INPUT kW 115 °F...
  • Page 15: Two Ton Air Performance

    036-21366-007-A-1205 TABLE 9: TWO TON AIR PERFORMANCE MODEL # (Cooling/ Heating) SIDE SUPPLY AIR PERFORMANCE - 208 VOLT SIDE SUPPLY AIR BLOWER PERFORMANCE - 230 VOLT BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208 VOLT BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 230 VOLTS Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters.
  • Page 16: Side Supply Air Blower Performance - 208/230 Volts

    TABLE 10: SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS MODEL # MODE (COOLING / HEATING) COOLING (FACTORY SETTING) COOLING (FIELD SETTING) HEATING (2 TUBE) (FACTORY SETTING) HEATING (3 TUBE) (FACTORY SETTING) COOLING (FACTORY SETTING) COOLING (FIELD SETTING) HEATING (2 TUBE) (FACTORY SETTING) HEATING (3 TUBE) (FACTORY SETTING)
  • Page 17: Bottom Supply Air Blower Performance - 208/230 Volts

    036-21366-007-A-1205 TABLE 11: BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS MODEL # MODE (COOLING / HEATING) COOLING (FACTORY SETTING) COOLING (FIELD SETTING) HEATING (2 TUBE) (FACTORY SETTING) HEATING (3 TUBE) (FACTORY SETTING) COOLING (FACTORY SETTING) COOLING (FIELD SETTING) HEATING (2 TUBE) (FACTORY SETTING) HEATING (3 TUBE) (FACTORY SETTING)
  • Page 18: Field Wiring Diagram Control Wiring

    TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON DESCRIPTION WET EVAPORATOR COIL ECONOMIZER FILTER FRAME KIT The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
  • Page 19: Power Wiring Field Diagram

    036-21366-007-A-1205 FIGURE 4 - POWER WIRING FIELD DIAGRAM TABLE 14: ELECTRICAL DATA VOLTAGE LIMITATIONS MODEL POWER SUPPLY MIN. MAX. 208/230-1-60 208/230-1-60 208/230-3-60 460-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 Rated in accordance with ARI Standard 110, utilization range “A”. Dual element, time delay type.
  • Page 20: Unit Dimensions - Front

    B L O W E R S E R V I C E A C C E S S C O M P A R T M E N T P A N E L G A S S U P P L Y 1 - 1 / 4 "...
  • Page 21: Unit Dimensions - Front & Bottom

    036-21366-007-A-1205 HIGH VOLTAGE CONN. 1-3/32" DIA. KNOCKOUT CONDENSATE DRAIN 3/4"' NPTI FIGURE 6 - UNIT DIMENSIONS - FRONT & BOTTOM FIGURE 7 - UNIT DIMENSIONS - BACK & BOTTOM Unitary Products Group 19-1/4 11-7/8 8-7/8 26-3/4 FRONT GAS SUPPLY 1-5/8" DIA. KNOCKOUT (1/2"...
  • Page 22: Typical Slab On Ground Installation

    036-21366-007-A-1205 FIGURE 8 - TYPICAL SLAB ON GROUND INSTALLATION FIGURE 9 - TYPICAL ROOF CURB INSTALLATION Unitary Products Group...
  • Page 23: Typical Duct Applications

    036-21366-007-A-1205 FIGURE 10 - TYPICAL DUCT APPLICATIONS TABLE 17: UNIT WEIGHTS AND CENTER OF GRAVITY SHIPPING UNIT WEIGHT SIZE (lbs.) 024, 030, 036 042, 048, 060 "A" 49-1/8 FIGURE 11 - UNIT CENTER OF GRAVITY Unitary Products Group CORNER WEIGHTS OPERATING (location, lbs.) WEIGHT...
  • Page 24: Roof Curb Dimensions

    036-21366-007-A-1205 FIGURE 12 - ROOF CURB DIMENSIONS FIGURE 13 - ROOF CURB CROSS SECTION 1. 8” Roof curb also available Unitary Products Group...
  • Page 25: Typical Wiring Diagram D*Np 024 (208/230-1-60 Power Supply)

    036-21366-007-A-1205 FIGURE 14 - TYPICAL WIRING DIAGRAM D*NP 024 (208/230-1-60 POWER SUPPLY) Unitary Products Group...
  • Page 26: Typical Wiring Diagram D*Np 030-048 (208/230- 1-60 Power Supply)

    036-21366-007-A-1205 NEUTRAL DELAY DELAY FIGURE 15 - TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230-1-60 POWER SUPPLY) Unitary Products Group...
  • Page 27: Typical Wiring Diagram D*Np 060 (208/230-1-60 Power Supply)

    036-21366-007-A-1205 FIGURE 16 - TYPICAL WIRING DIAGRAM D*NP 060 (208/230-1-60 POWER SUPPLY) Unitary Products Group...
  • Page 28: Typical Wiring Diagram D*Np 030-048 (208/230- 3-60 Power Supply)

    036-21366-007-A-1205 NEUTRAL DELAY DELAY FIGURE 17 - TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230-3-60 POWER SUPPLY) Unitary Products Group...
  • Page 29: Typical Wiring Diagram D*Np 060 (208/230-3-60 Power Supply)

    036-21366-007-A-1205 FIGURE 18 - TYPICAL WIRING DIAGRAM D*NP 060 (208/230-3-60 POWER SUPPLY) Unitary Products Group...
  • Page 30: Typical Wiring Diagram D*Np 030-048 (460/575-3-60 Power Supply)

    036-21366-007-A-1205 FIGURE 19 - TYPICAL WIRING DIAGRAM D*NP 030-048 (460/575-3-60 POWER SUPPLY) Unitary Products Group...
  • Page 31: Typical Wiring Diagram D*Np 060 (460/575-3-60 Power Supply)

    036-21366-007-A-1205 FIGURE 20 - TYPICAL WIRING DIAGRAM D*NP 060 (460/575-3-60 POWER SUPPLY) Unitary Products Group...
  • Page 32: Typical Wiring Diagram Notes

    TYPICAL WIRING DIAGRAM NOTES All field wiring to be accomplished following city, local and/or national codes in effect at time of installation of this unit. Caution: Label all wires prior to disconnection when ser- vicing controls. Wiring errors can cause improper and dangerous operation if any of the wire as supplied with this unit must be removed it must be replaced with type 105°C, 600V wire or equivalent clearly renumbered for...
  • Page 33: Mechanical Specifications

    MECHANICAL SPECIFICATIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK’s DNP is a unit that gives you the flexibility and choices you need in today’s market. These packaged cooling/heating air conditioners are designed for outdoor installation.
  • Page 34 UNIT OPERATING CHARACTERISTICS Unit shall be capable of starting and running at 125º F out- door temperature, exceeding maximum load criteria ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 45º F outdoor tempera- ture.
  • Page 35 036-21366-007-A-1205 Unitary Products Group...
  • Page 36 Subject to change without notice. Printed in U.S.A. Copyright © 2005 by Unitary Products Group. All rights reserved. Unitary Products Group Supersedes: 036-21366-006-A-1005 5005 York Drive 036-21366-007-A-1205 Norman 73069...