3.Defrost Interval; 4.Low Ambient Cooling; 5.Quiet Shift - Bryant Evolution Connex SYSTXBBECW01-A Installation Instructions Manual

Evolution connex control
Hide thumbs Also See for Evolution Connex SYSTXBBECW01-A:
Table of Contents

Advertisement

Cooling Lockout Temp: None, 45, 50 or 55 (_F)
S
Default = None
d
6.3.4.3.
Defrost Interval
Time interval at which defrost cycles can occur on a heat pump. AUTO means the
defrost interval is optimized by the outdoor control. After the selection is made,
touch SAVE.
Set Defrost Interval: 30, 60, 90, 120 minutes or AUTO
S
Default = AUTO
d
NOTE: See Heat Pump Installation Instructions for Defrost Timing Interval when
using AUTO Defrost.
6.3.4.4.
Low Ambient Cooling
Selecting YES will enable the low ambient cooling operation in the outdoor unit.
This setting is only available with communicating outdoor units and with Cooling
Lockout set to NONE. Low ambient kits are not needed with communicating
outdoor units. After the selection is made, touch SAVE.
Low Ambient Cooling: Yes or No
S
Default = No
d
6.3.4.5.
Quiet Shift
This option turns on Quiet Shift function in 1- - stage or 2- - stage communicating heat
pumps. After the selection is made, touch SAVE.
NOTE: This option is not available with variable speed heat pumps.
Quiet Shift: On or Off
S
Default = Off
d
42