BLOWER PERFORMANCE SPECIFICATIONS
GMV95 Continuous Fan Speed Chart
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as
needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating
plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM minimum.
14
GMV950453BX*
Cooling
CFM at
Adjust
Speed
.1" - .8"
Tap
Tap
w.c. ESP
Minus(-)
380*
A
Normal
380*
Plus (+)
380*
Minus(-)
403
B
Normal
448
Plus (+)
493
Minus(-)
504
C
Normal
560
Plus (+)
616
Minus(-)
505
D
Normal
672
Plus (+)
739
GMV950905DX*
Cooling
CFM at
Adjust
Speed
.1" - .8"
Tap
Tap
w.c. ESP
Minus(-)
513*
A
Normal
513*
Plus (+)
513*
Minus(-)
554
B
Normal
616
Plus (+)
678
Minus(-)
706
C
Normal
784
Plus (+)
862
Minus(-)
907
D
Normal
1008
Plus (+)
1109
GMV950704CX*
Cooling
CFM at
Adjust
Speed
.1" - .8"
Tap
Tap
w.c. ESP
Minus(-)
380*
A
Normal
380*
Plus (+)
380*
Minus(-)
403
B
Normal
448
Plus (+)
493
Minus(-)
554
C
Normal
616
Plus (+)
678
Minus(-)
720
D
Normal
800
Plus (+)
880
GMV951155DX*
Cooling
CFM at
Adjust
Speed
.1" - .8"
Tap
Tap
w.c. ESP
Minus(-)
514*
A
Normal
514*
Plus (+)
514*
Minus(-)
554
B
Normal
616
Plus (+)
678
Minus(-)
706
C
Normal
784
Plus (+)
862
Minus(-)
907
D
Normal
1008
Plus (+)
1109