Goodman ComfortNet ACVC9 Technical Manu Technical Manualal

90% up to 96% gas furnace units
Hide thumbs Also See for ComfortNet ACVC9:

Advertisement

TECHNICAL MANU
TECHNICAL MANU AL
TECHNICAL MANU
TECHNICAL MANU
TECHNICAL MANU
TM
90%
UP TO
Refer to Service Manual RS6612002 for troubleshooting information.
Refer to the appropriate Parts Catalog for part number information.
Models listed on page 3.
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does
not assume any responsibility for property damage or personal injury due to improper service
procedures performed by an unqualified person.
®
is a registered trademark of Maytag Corporation or its related companies and is used under license to
®
ACVC9/AMVC95
GCVC9/GMVC95
96% Gas Furnace Units
Goodman Company, L.P., Houston, TX. All rights reserved.
Copyright ©2012-2013 Goodman
AL
AL
AL
AL
Company, L.P.
RT6612025r5
November 2013

Advertisement

Table of Contents
loading

Summary of Contents for Goodman ComfortNet ACVC9

  • Page 1 Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does RT6612025r5 not assume any responsibility for property damage or personal injury due to improper service procedures performed by an unqualified person.
  • Page 2: High Voltage

    Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Goodman will not be responsible Installation and repair of this unit WARNING WARNING...
  • Page 3 WARNING that is not design certified by damage, personal injury, or death, Goodman for use with this unit. do not store combustible materials or use gasoline or Serious property damage, personal injury, reduced unit other flammable liquids or vapors in the vicinity of this performance and/or hazardous conditions may result appliance.
  • Page 4: Product Design

    PRODUCT DESIGN Notes: General Operation Models covered by this manual come with a new 4-wire com- 1. Installer must supply one or two PVC pipes: one for com- municating PCB. When paired with a compatible communi- bustion air (optional) and one for the flue outlet (required). cating indoor unit and a CTK0* communicating thermostat, Vent pipe must be either 2”...
  • Page 5 PRODUCT DESIGN High Altitude Derate High altitude kits are purchased according to the installa- When this furnace is installed at high altitude, the appropri- tion altitude and usage of either natural or propane gas. Refer ate High Altitude orifice kit must be installed. This is re- to the chart below for a tabular listing of appropriate altitude quired due to the natural reduction in the density of both the ranges and corresponding manufacturer’s high altitude Natu-...
  • Page 6: Component Identification

    COMPONENT IDENTIFICATION N OTICE H o ri z ont a l C onn ect i o ns- Lef t S i de H o ri z ont al C o n n ect i o ns- R i ght S i d e 0140F00 821 N O TIC E Thi s f i t t i n g i s s p ec i al l y d esi g n ed t o...
  • Page 7 PRODUCT DIMENSIONS GMVC95/AMVC95___X*...
  • Page 8 PRODUCT DIMENSIONS GCVC9/ACVC9_____X*...
  • Page 9 PRODUCT DESIGN PRESSURE SWITCH TRIP POINTS AND USAGE CHART NEGATIVE PRESSURE NEGATIVE PRESSURE NEGATIVE PRESSURE NEGATIVE PRESSURE ID BLOWER ID BLOWER COIL COVER COIL COVER WITH FLUE WITH FLUE WITH FLUE WITH FLUE NOT FIRING FIRING NOT FIRING FIRING MODEL TYPICAL SEA LEVEL TYPICAL SEA LEVEL TYPICAL S EA LEVEL...
  • Page 10 PRODUCT DESIGN...
  • Page 11 PRODUCT DESIGN PRIMARY LIMIT Part Number 20162903 20162904 20162905 20162907 20162908 0130F001 05 Open Setting (°F) GMVC950453BX* AMVC950453BX* GMVC950704CX* AMVC950704CX* GMVC950905CX* AMVC950905CX* GMVC950905DX* AMVC950905DX* GMVC951155DX* AMVC951155DX* GCVC950714CX* ACVC950714CX* GCVC950915DX* ACVC950915DX* GCVC91155DX* ---- ---- ---- ---- ACVC951155DX* ROLLOUT LIMIT SWITCHES Part Number 10123512 1012 3517 10123518...
  • Page 12 PRODUCT DESIGN Thermostats: ComfortNet™ CTK0* Thermostat Kit Filters: Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty Upflow Filters Return air filters may be installated at the furnace side and/or bottom return openings.
  • Page 13 PRODUCT DESIGN UPFLOW COOLING AIRFLOW REQUIREMENT (CFM) 1000 1200 1400 1600 1800 2000 0453__X* 207* 207* 0704__X* 318* 318* 0905__X* 413* 413* 413* 1155__X* 437* 437* 437* COUNTERFLOW COOLING AIRFLOW REQUIREMENT (CFM) 1000 1200 1400 1600 1800 2000 0714__X* 316* 316* 0915__X* 409*...
  • Page 14 FURNACE SPECIFICATIONS A/GMVC95 *MVC950453 *MVC950704 *MVC950905 *MVC950905 *MVC951155 MODEL BTUH Natural Gas Input (High Fire) 45,000 68,000 90,000 90,000 113,000 Natural Gas Output (High Fire) 43,200 65,300 86,500 86,500 108,600 LP Gas Input (High Fire) 40,500 61,200 81,000 81,000 101,700 LP Gas Output (High Fire) 38,900 58,800...
  • Page 15 FURNACE SPECIFICATIONS A/GCVC9 GCVC91155 ACVC951155 *CVC950714 *CVC950915 MODEL BTUH Natural Gas Input (High Fire) 1 13,000 113,000 68,000 90,000 Natu ral Gas Output (Hig h Fire) 1 05,100 105,100 64,600 85,500 LP Gas Input (High Fire) 1 01,700 101,700 61,200 81,000 LP Gas Output (High Fi re) 94,600...
  • Page 16: Blower Performance Specifications

    BLOWER PERFORMANCE SPECIFICATIONS *MVC950453BX Cooling/Heating Speed Charts *MVC950453BX *MVC950453BX Cooling Speed Heating Speed ( @ .1" - .8" w.c. ESP) (@ .1" - .5" w.c. ESP; Rise Range: 30 - 60°F) High-Stage Low-Stage High-Stage Low-Stage Rise Adjust Adjust (°F) Minus 10% Minus 10% Minus 5% Minus 5%...
  • Page 17 BLOWER PERFORMANCE SPECIFICATIONS *MVC950905CX Cooling/Heating Speed Charts *MVC950905CX *MVC950905CX Cooling Speed Heating Speed ( @ .1" - .8" w.c. ESP) (@ .1" - .5" w.c. ESP; Rise Range: 30 - 60°F) High-Stage Low-Stage High-Stage Low-Stage Rise Adjust Adjust (°F) Minus 10% Minus 10% 1,341 Minus 5%...
  • Page 18 BLOWER PERFORMANCE SPECIFICATIONS *MVC951155DX Cooling/Heating Speed Charts *MVC951155DX *MVC951155DX Cooling Speed Heating Speed ( @ .1" - .8" w.c. ESP) (@ .1" - .5" w.c. ESP; Rise Range: 35 - 65°F) High-Stage Low-Stage High-Stage Low-Stage Rise Adjust Adjust (°F) Minus 10% Minus 10% 1,594 1,107...
  • Page 19 BLOWER PERFORMANCE SPECIFICATIONS *CVC950714CX Cooling/Heating Speed Charts *CVC950714CX *CVC950714CX Cooling Speeds Heating Speed ( @ .1" - .8" w.c. ESP) (@ .1" - .5" w.c. ESP; Rise Range: 25 - 55°F) High-Stage Low-Stage High-Stage Low-Stage Adjust Adjust Rise Minus 10% Minus 10% 1,107 Minus 5%...
  • Page 20 BLOWER PERFORMANCE SPECIFICATIONS GCVC951155DX Cooling/Heating Speed Charts GCVC91155DX* GCVC91155DX* ACVC951155DX* ACVC951155DX* Cooling Speeds He ating Speeds (@.1" -.8" w.c. ESP) (@.1" -.5" w.c. ESP; Rise Range: 40 - 70°F) High-Stage Low-Stage High-Stage Low-Stage Adjust Adjust Rise 1,093 Minus 10% Minus 10% 1,583 Minu s 5% Minus 5%...
  • Page 21 BLOWER PERFORMANCE SPECIFICATIONS Circulator Blower Speed Adjustment Switches Dip Switch Switch Bank Purpose Function Heating Off Delay 2 Stage Stat 2 Stage Stat Thermostat Setup 1 Stg Stat 5 min delay 1 Stg Stat auto delay Cooling Airflow Add 5% Minus 5% Trim Add 10%...
  • Page 22 BLOWER PERFORMANCE SPECIFICATIONS Ramping Profile Note: The multi-speed circulator blower also offers several custom ON/OFF ramping profiles. These profiles may be used to enhance cooling performance and increase comfort level. The ramping profiles are selected using DIP switches 5 and 6.
  • Page 23: Wiring Diagrams

    WIRING DIAGRAMS *CVC9/*MVC95_A* HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 24 ANSI Z21.20 AUTOMATIC IGNITION SYSTEM 24VAC 60Hz 0.8 A. MAX. BLOWER ASSEMBLY SCHEMATIC ACVC9/AMVC95/GCVC9/GMVC95_____X* MODEL FURNACES This schematic is for reference only. Not all wiring is as shown above, refer to the appropriate wiring diagram for the unit being serviced.
  • Page 25 SCHEMATICS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.