Goodman GMV950453BX Series Technical Information Manual

Goodman GMV950453BX Series Technical Information Manual

40" 95% gas furnace units/40" 90% gas furnace units

Advertisement

TECHNICAL INFORMATION MANUAL
GMV95 40" 95% Gas Furnace Units
GCV9 40" 90% Gas Furnace Units
Refer to Service Manual RS6610004* for installation,
operation, and troubleshooting information.
All safety information must be followed as provided in
the Service Manual.
Refer to the appropriate Parts Catalog for part number
information.
This manual is to be used by qualified, professionally trained HVAC
®
technicians only. Goodman does not assume any responsibility for property
damage or personal injury due to improper service procedures performed by
an unqualified person.
Copyright ©
2005 - 2008 Goodman Manufacturing Company, L.P.
Models listed
on page 2.
RT6612012 Rev. 2
July 2008

Advertisement

Table of Contents
loading

Summary of Contents for Goodman GMV950453BX Series

  • Page 1 TECHNICAL INFORMATION MANUAL GMV95 40" 95% Gas Furnace Units GCV9 40" 90% Gas Furnace Units Models listed on page 2. • Refer to Service Manual RS6610004* for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual.
  • Page 2: Product Identification

    PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. 95 045 3 B Product Type Design Series G: Goodman Brand A: Initial Release Additional Features Supply Type N: Natural Gas...
  • Page 3 PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. GMV950453BX* GMV950704CX* GMV950905DX* GMV951155DX* GCV90704CX* GCV90905DX* GCV91155DX* The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants WARNING WARNING...
  • Page 4: Product Design

    PRODUCT DESIGN General Operation 3. Conversion kits for propane gas and high altitude natural and propane gas operation are available. See The GMV95 and GCV9 furnaces are equipped with an elec- tronic ignition device to light the burners and an induced draft High Altitude Derate chart for details.
  • Page 5 PRODUCT DESIGN High Altitude Derate When this furnace is installed at high altitude, the appropriate High Altitude orifice kit must be installed. This is required due to the natural reduction in the density of both the gas fuel and combustion air as altitude increases. The kit will provide the proper design certified input rate within the specified altitude range.
  • Page 6: Component Identification

    COMPONENT IDENTIFICATION Intell-Ignition Counterflow /Horizontal Upflow/Horizontal Two-Stage Gas Valve Coil Front Cover Pressure Tap Gas Line Entrance (Alternate) Coil Front Cover Drain Port Pressure Switch(es) Drain Line Penetrations Gas Manifold Drain Trap Combustion Air Intake Connection Blower Door Interlock Switch Hot Surface Igniter Inductor (Not All Models) Rollout Limit...
  • Page 7: Product Dimensions

    PRODUCT DIMENSIONS GMV95___XA DISCHARGE DISCHARGE INTAKE PIPE 2" PVC RIGHT SIDE 1 1/2 DRAIN LINE HOLES 1 5/8 UNFOLDED FLANGES UNFOLDED FLANGES FOLDED FLANGES FOLDED FLANGES RIGHT SIDE VIEW Cabinet Size GMV950453BX* 17-1/2 12-15/16 12-1/8 13-5/8 GMV950704CX* 19-1/2 15-15/16 17-1/2 GMV950905DX* 24-1/2 20-7/16...
  • Page 8 PRODUCT DIMENSIONS GCV9_____XA LEFT SIDE FRONTVIEW RIGHT SIDE VIEW VIEW 28 3/4 2 1/2 VENT/FLUE PIPE 20 1/4 (RETURN AIR) AIR INTAKE PIPE 2" PVC 2" PVC CONDENSATE DRAIN TRAP LOW VOLTAGE 1 3/4 ELECTRICAL HOLE w/ 3/4" PVC 1 3/4 DISCHARGE LOW VOLTAGE HIGH VOLTAGE...
  • Page 9 PRODUCT DESIGN PRESSURE SWITCH TRIP POINTS AND USAGE CHART NEGATIVE NEGATIVE NEGATIVE NEGATIVE PRESSURE PRESSURE PRESSURE PRESSURE ID BLOWER ID BLOWER COIL COVER COIL COVER WITH FLUE WITH FLUE WITH FLUE WITH FLUE NOT FIRING FIRING NOT FIRING FIRING MODEL TYPICAL SEA TYPICAL SEA TYPICAL SEA...
  • Page 10: Rollout Limit Switches

    PRODUCT DESIGN PRIMARY LIMIT Part Number 20162903 20162904 20162905 20162907 20162908 Open Setting (°F) ---- ---- ---- ---- GMV950453BX* GMV950704CX* ---- ---- ---- ---- GMV950905DX* ---- ---- ---- ---- GMV951155DX* ---- ---- ---- ---- GCV90704CX* ---- ---- ---- ---- GCV90905DX* ---- ---- ----...
  • Page 11 PRODUCT DESIGN Coil Matches: ® A large array of Goodman brand coils are available for use with the GMV95 & GCV9 model furnaces, in either upflow or horizontal applications. These coils are available in both cased and uncased models, with or without a TXV expansion device.
  • Page 12 PRODUCT DESIGN Thermostats: The following 2-stage thermostats are recommended for use with GMV95 & GCV9 Furnace Models: THERMOSTATS Thermostat Mechanical / Digital CHT90-120 Cooling/Heating, Mechanical CH70TG Cooling/Heating, Digital, Non-programmable CHSATG Cooling/Heating, Mechanical Heating Only, Mechanical H20TWR Filters: Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or CAN/ULCS111 standards.
  • Page 13 PRODUCT DESIGN UPFLOW UPFLOW COOLING AIRFLOW REQUIREMENT (CFM) COOLING AIRFLOW REQUIREMENT (CFM) 1000 1200 1400 1600 2000 1000 1200 1400 1600 2000 0453__X* 207* 207* 0453__X* 415* 415* 0704__X* 318* 318* 0704__X* 636* 636* 0905__X* 413* 413* 413* 0905__X* 826* 826* 826* 1155__X*...
  • Page 14: Furnace Specifications

    FURNACE SPECIFICATIONS GMV95 MODEL GMV950453BX* GMV950704CX* GMV950905DX* GMV951155DX* Btuh Input (US) High Fire 46,000 69,000 92,000 115,000 Output (US) High Fire 44,300 66,900 88,800 111,100 Btuh Input (US) Low Fire 32,000 48,000 64,000 80,000 Output (US) Low Fire 30,800 46,400 61,700 77,400 A.F.U.E.
  • Page 15 FURNACE SPECIFICATIONS GCV9 MODEL GCV90704CX* GCV90905DX* GCV91155DX* Btuh Input (US) High Fire 69,000 92,000 115,000 Output (US) High Fire 64,200 84,000 109,000 Btuh Input (US) Low Fire 48,000 64,000 80,000 Output (US) Low Fire 45,000 60,100 77,400 A.F.U.E. Rated External Static (" w.c.) .10 - .50 .10 - .50 .10 - .50...
  • Page 16: Blower Performance Specifications

    BLOWER PERFORMANCE SPECIFICATIONS GMV95 Heating Speed Charts GMV950453BX* (Rise Range: 30 - 60°F) GMV950704CX* (Rise Range: 30 - 60°F) Low Stage High Stage Low Stage High Stage Heating Heating Adjust Rise Adjust Rise Speed Speed at .1" - .5" at .1" - .5" (°F) at .1"...
  • Page 17 BLOWER PERFORMANCE SPECIFICATIONS GMV95 High (Single) Stage Cooling Speed Charts GMV950453BX* GMV950704CX* GMV950905DX* GMV951155DX* Cooling CFM at Cooling CFM at Cooling CFM at Cooling CFM at Adjust Adjust Adjust Adjust Speed .1" - .8" Speed .1" - .8" Speed .1" - .8" Speed .1"...
  • Page 18 BLOWER PERFORMANCE SPECIFICATIONS GMV95 Continuous Fan Speed Chart GMV950453BXC* GMV950704CX* Cooling CFM at Cooling CFM at Adjust Adjust Speed .1" - .8" Speed .1" - .8" w.c. ESP w.c. ESP Minus(-) 380* Minus(-) 380* Normal 380* Normal 380* Plus (+) 380* Plus (+) 380*...
  • Page 19 BLOWER PERFORMANCE SPECIFICATIONS GCV9 Heating Speed Charts GCV90704CX* GCV90905DX* (Rise Range: 30 - 60°F) (Rise Range: 30 - 60°F) Low Stage High Stage Low Stage High Stage Heating Heating Adjust Rise Adjust Rise Speed Speed at .1" - .5" w.c. at .1"...
  • Page 20 BLOWER PERFORMANCE SPECIFICATIONS GMV95/GCV9 Circulator Blower Speed Adjustment Switches Note: There is a green LED adjacent to the integrated control module fuse which is used to verify airflow volume. The green CFM LED blinks once for each 100 CFM of airflow.
  • Page 21 BLOWER PERFORMANCE SPECIFICATIONS GCV9 Continuous Fan Speed Chart GCV90704CX* GCV90905DX* GCV91155DX* Cooling CFM at Cooling CFM at Cooling CFM at Adjust Adjust Adjust Speed .1" - .8" w.c. Speed .1" - .8" w.c. Speed .1" - .8" w.c. Minus(-) 380* Minus(-) 513* Minus(-)
  • Page 22 BLOWER PERFORMANCE SPECIFICATIONS GCV9 Low Stage Cooling Speed Charts GCV90704CX* GCV90905DX* GCV91155DX* Cooling CFM at Cooling CFM at Cooling CFM at Adjust Adjust Adjust Speed .1" - .8" Speed .1" - .8" Speed .1" - .8" w.c. ESP w.c. ESP w.c.
  • Page 23 PERFORMANCE...
  • Page 24: Wiring Diagrams

    GMV95/GCV9 WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. 40 V A T R A N S - F O R M E R...
  • Page 25 SCHEMATICS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. LINE XFMR CIRC XFMR LINE PARK COOL HEAT SINGLE HEAT BLOWER ASSEMBLY SCHEMATIC GMV95/GCV9_____X* MODEL FURNACES This schematic is for reference only.
  • Page 26 SCHEMATICS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.