Standard Auto Or Manual-Changeover Two-Stage Heat/Two-Stage Cool Specs; Configuration Settings For Internal Control Touchpad - Daikin IM 1193 Installation & Maintenance Data

Packaged terminal air conditioner 16" x 42" pgan with top-mounted hydronic heat
Table of Contents

Advertisement

Standard Auto or Manual-Changeover
Two-Stage Heat/ Two-Stage Cool Specs
Part No. 910116774 (1-Pk, White with Wall Plate)
Specifications
Electrical Rating:
24 VAC (18 to 30 VAC)
1 amp maximum per terminal
4 amp maximum total load
30-minute power loss memory retention
Easy access terminal block
Temperature Control Ranges:
45°F to 90
F, Accuracy: ± 1°F
o
System Configurations:
Single or two-stage heat/cool
Single or two-stage heat pump
Terminations:
R, C, W1/O/B, Y1, W2, Y2, G
IM 1193 / Page 20 of 32
Configuration Settings for Internal Control
Touchpad
7-Button Touchpad with Display
The control can be configured to operate a wide range of op-
tions. The options listed below with the * are the factory de-
fault settings. If these are acceptable, then the unit does not
require any additional configuration and is fully operable. To
configure the unit, first select the configuration feature code
setting and then an option code to change from the factory
default setting.
The Internal Control Board must be set up for Remote
Thermostat Operation, configuration mode "C-1" and Option
code "L-5, as the Daikin Touchpad controller is connected to
the "Remote Thermostat" terminals on the Internal Control
Board.
To enter configuration feature mode:
1. Press and hold the up and down arrow keys at the same
time and press the OFF key twice within a two (2)
second time frame. The display will indicate - -., and
then release the key and press the key one time. The
display will then alternate between C1 and 0.
To select a different configuration feature code, press the
HEAT key until the desired configuration comes up. To
scroll to a previously viewed configuration codes press
the COOL key.
Once you have scrolled to the correct feature, then to
select the option code for your desired configuration,
press either the up or down key to scroll through the
options of the selected feature code.
To exit configuration mode:
1. Press the OFF key. Configuration feature mode will
also exit if no keys are pressed for a period of two (2)
minutes.