Daikin ExtendAire IM 871-3 Installation & Maintenance Data
Daikin ExtendAire IM 871-3 Installation & Maintenance Data

Daikin ExtendAire IM 871-3 Installation & Maintenance Data

Ptac for pdae/pdhe & pdaf/pdhf & optional boost fan installation

Advertisement

Quick Links

Applied PTAC ExtendAire™ for Models PDAE/PDHE
& PDAF/PDHF & Optional Boost Fan Installation
For Adjoining Room Applications
General
Proper installation of the ExtendAire conditioner described
herein requires strict adherence to these installation
instructions.
Description
The ExtendAire conditioner is a cabinet extension kit designed
to provide balanced heating and cooling in two rooms using a
single Incremental conditioner. Components of the ExtendAire
are shown in
Figure 1
and listed in
Unpacking
Open the carton and check the contents. Report missing or
damaged parts to the carrier immediately.
!
CAUTION
Sharp metal edges are a hazard, use care when servicing to
avoid contact with them.
Table 1: ExtendAire Duct Extension Option
Description
Primary Discharge Section
Shelf Discharge Assembly - Primary Discharge Section
Shelf Discharge Assembly - 3-Foot Extension Section
Shelf Discharge Assembly - Shelf Discharge Section
Shelf Discharge Assembly - Trim Piece
Shelf Discharge Assembly - End Cap
2
Side Wall Outlet Assembly
2
Side Wall Outlet Assembly
2
Side Wall Outlet Assembly
2
Side Wall Outlet Assembly
1
Notes:
Control door and end cap are included in Primary Discharge Section.
2
Discharge grille in adjoining room to be supplied by others. Additional 3-foot extension sections must be ordered in
packages as shown in
Table 2: Supplementary Accessories
Description
3-Foot Extension Section Pack - 3-Foot Extension
3-Foot Extension Section Pack - Trim Piece
NOTICE
When a 3 foot (or greater) extension section is added to the pri-
mary discharge section, the (optional) boost fan is recommend-
ed. The Boost Fan operates when the indoor fan operates, to
assist unit airflow into the adjoining room.
©2013 Daikin Applied • www.DaikinAP.com • (800) 432-1342
Installation & Maintenance Data
Table
1.
1
1
1
- Primary Discharge Section
- 3-Foot Extension Section
- Trim Piece
- End Cap
Table
2.
Figure 1: ExtendAire Component Descriptions
1. End Cap
2. 3' Extension Section
3. Shelf Discharge Section
4. Primary Discharge Section
5. Trim Piece
Quantity in
Each Package
1
1
1
1
2
2
1
1
1
1
Quantity in
Each Package
2
2
IM 871-3
Group: Applied PTAC/HP
Part Number: 910116725
Date: October 2011
Part Number
910106134
910106137
910106138
Part Number
061389601

Advertisement

loading

Summary of Contents for Daikin ExtendAire IM 871-3

  • Page 1 When a 3 foot (or greater) extension section is added to the pri- mary discharge section, the (optional) boost fan is recommend- ed. The Boost Fan operates when the indoor fan operates, to assist unit airflow into the adjoining room. ©2013 Daikin Applied • www.DaikinAP.com • (800) 432-1342...
  • Page 2 ExtendAire & Optional Boost Fan 3. Bend the hold down tabs on the underside of the cabinet/ wall sleeve grille tray and control door assembly 90º and Installation Procedure Models PDAE remove grille tray (Figure and PDHE Figure 4: Typical Wall Construction Types CAUTION Installation and maintenance is to be performed only by qualified personnel who are familiar with, and in compliance with state, lo-...
  • Page 3 4. Snap control pad into the primary discharge section control Relocating the Control Pad pad opening. Before reinstalling the chassis into the cabinet/wall sleeve, do To continue the ExtendAire installation refer to "ExtendAire™ the following: Installation Procedure Common to Models PDAE/PDHE and 1.
  • Page 4 ExtendAire & Optional Boost Fan 3. Remove the two (2) screws located at each end of the cabinet wrap securing it to the wall sleeve. Lift slightly, Installation Procedure Models PDAF and pull the cabinet wrap away from the unit chassis/wall and PDHF sleeve (Figure...
  • Page 5 Figure 10: Position and tighten screws on mounting brackets to secure primary discharge section to cabinet/wall sleeve Mounting Bracket Detail Mounting Bracket Assembly Primary Discharge Section Locate Right and Left Mounting Bracket 6. Remove the grilles at the right and left ends of the primary Figure 11: Reinstall the touchpad communication cable and the touchpad bezel discharge section...
  • Page 6 Figure 12: Typical Wall Construction Types *12" Wall 8.5" Wall Primary Discharge 8.5" 12" Primary Discharge 11" Section 11" Section 1.25" 3" 11.5" 5.25" 8.75" 8.75" 23.5" 13.75" Note: *12" Wall Requires a 14.75" Deep Wall Sleeve Configuration 1 ExtendAire™ Installation Procedure Common to Models PDAE/PDHE and PDAF/ Shelf Discharge Assembly (Refer to Figure...
  • Page 7 Configuration 2 2. Determine capacity requirements from the "ExtendAire Capacity Selection", Table 3, Table 4 or Table 5 and place Side Wall Outlet Assembly (Refer to Figure required number of active grilles in space provided in top a. Butt end of one “L” shaped piece (rear half) of 3' Extension section.
  • Page 8 ExtendAire™ (Optional) Boost Fan Figure 15: Remove the two (2) screws holding control box to the chassis Installation Procedure Common to Models PDAE/PDHE and PDAF/PDHF Control Box Assembly Parts in Kit Remove two (2) screws holding control box assembly to chassis 1.
  • Page 9 7. Disconnect the wire connectors along the left side of the Figure 18: Cut two wires on the fan connector, (orange and control board as numbered 1, 2, 3, 4 , 5 & 6 in purple), 2 inches back from the board connector Figure Figure 17: Disconnect the wire connectors along the left side of the control board, numbered 1, 2, 3, 4, 5 &...
  • Page 10 10. Feed the (green) ground wire from the boost fan motor 14. Re-attach all sensors and connectors to the appropriate harness through one of the three wiring grommets at the terminals along the left side of the control board. Replace bottom section of the control box and attach it to the the control box cover in reverse order as described in existing ground screw as shown in...
  • Page 11 Figure 22: Boost Fan assembly details Boost fan power cord secured with two (2) zip ties in primary section Detail Boost fan positioned midway inside extension section Removed right end and left end grilles Zip-tie location (1) in 3' extension section Trim piece Primary discharge air section Boost fan power cord plug...
  • Page 12 Daikin Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinAP.com and click on training, or call 540-248-9646 and ask for the Training Department.

This manual is also suitable for:

910116725