Vent Installation; Installation Precautions - Majestic 500DVH Series Installation And Operating Instructions Manual

Dvh series direct vent gas fireplace
Table of Contents

Advertisement

This fireplace must be vented to the outside. The venting system must NEVER be
attached to a chimney serving a separate solid fuel burning appliance. Each gas
appliance must use a separate vent system. Do not use common vent systems.
Horizontal sections of this vent system
require a minimum of 3" clearances to
combustibles at the top of the flue and 1"
clearance at the sides and bottom until the
flue penetrates the outside wall. A minimum
1" clearance all around the flue is acceptable
at this point of penetration.
Vertical sections of this vent system require
a minimum of 1" clearance to combustibles
on all sides of the pipe.
56D3049
Figure 8 - Combustible Clearances for Vent Pipe
Maintain 3"
1 "
3 "

VENT INSTALLATION

A Minimum of 3" Clearance
to the Top Is Required Along
Horizontal Length until Flue
Pipe Penetrates Outside Wall.
1 "
1 "
1 "
A Minimum 1"
Clearance to
Combustibles
Permitted All
Around Flue at
Outside Wall
13