Toshiba RAV-SM560AT-E Service Manual page 144

Air conditioner split type
Hide thumbs Also See for RAV-SM560AT-E:
Table of Contents

Advertisement

RAV-SM800UT-E
1. Cutting of Capillary Tube
A capillary tube ( 025
Cut and divide the tube to each length as shown below.
Ref No.
025
026
[Cutting]
Plane circumference of the capillary tube with
triangle file, etc., and then break off it.
2. Attachment of joint pipe
Insert the attached joint pipe into the end of the
capillary tube up to 15mm, and braze it.
Form the capillary tube as same as that in the
distributor assembly before replacement.
3. Brazing to indoor heat exchanger
Attach the capillary tube processed in items 1 and 2 to the end of the pipe with brazing as shown below.
025
026 : Inner diameter 2mm, Length 1000mm) is brazed to a distributor assembly.
No. of capillary tubes
7
10
Cutting
100 mm : 1 pc.
300 mm : 1 pc.
400 mm : 1 pc.
100 mm : 2 pcs.
150 mm : 1 pc.
500 mm : 4 pcs.
NOTE) Break off the capillary tube so
that inner diameter is not deformed
026
– 143 –
600 mm : 2 pcs.
700 mm : 1 pc.
800 mm : 1 pc.
600 mm : 2 pcs.
900 mm : 1 pc.