Toshiba RAV-SM560AT-E Service Manual page 132

Air conditioner split type
Hide thumbs Also See for RAV-SM560AT-E:
Table of Contents

Advertisement

[21 error] [
] LCD flash
NO
Check TE, TC, TS sensors.
Replace electron expansion valve.
Check charged refrigerant amount.
Check liquid/gas valves.
Check abnormal overload.
Is high-voltage
protective operation by
TE sensor normal?
YES
Is connection of cabling
Does cooling outdoor fan
normally operate?
YES
Is fan motor normal?
Does electron control
valve normally operate?
YES
Do not TD and TO sensors
come off the detection part?
Are characteristics of
TD, TO, TC sensor resistance
* For RAV-SM560AT-E, check control P.C. board.
NO
connector normal?
YES
NO
Is connection of
connector normal?
YES
YES
NO
values normal?
YES
* Refer to Characteristics-3 and 4.
Check CDB.
Defect
Replace
– 131 –
NO
Correct connection of
cabling connector.
Check TE sensor.
Defect
Replace
NO
Correct connection of
connector.
NO
Replace fan motor.
YES
Correct coming-off.
NO
Replace TD, TO,
and TC sensors.

Hide quick links:

Advertisement

Table of Contents
loading