Standard Mounting
Make sure the ceiling or wall is strong enough to support the
weight of the unit (See Table 1). Remove the mounting
brackets from the unit and secure to wall or ceiling as
required.
The unit must be level front to back and sloped 1/8" towards
condensate drain (See Figure 3).
Table 1: Unit Weight - lbs.
Model
20
Weight ID Unit
95
Weight OD Unit
125
Figure 3. Slope for condensate drainage
Ceiling Mount
Wall/Floor Mount
IM 820
25
30
40
50
99
99
154
154
128
209
220
231
1/8"
Slope
Slope
Semi-enclosed Mounting
In case the unit is to be half-recessed into a false ceiling,
make sure the unit is well-aligned with the ceiling.
Provide the installation space as shown in Figure 4.
Figure 4. Semi-enclosed Mounting
12" min.
23"
12" min.
1/2"
Mounting Surface
Ceiling Board
6.3/4"
48" min.
1/2" min.
Top Panel of Unit
22"
1/2"
1/2"
Page 7