Specifications

This section contains system specifications for both the 7311 Model D10 I/O
Subsystem, and the 7311 Model D20 I/O Subsystem

Model D10 Specifications

Dimensions
Height
Width
Depth
Weight
Electrical
Power source loading for two 7311-D10 (max.)
Voltage range
Frequency
Thermal output (typical)
Thermal output (max.)
Power requirements (typical)
Power requirements for two 7311-D10 (max.)
Power factor
Inrush current²
Maximum altitude
Temperature Requirements³
Humidity Requirements
(Noncondensing)
Wet Bulb
Noise Emissions
L
, one 7311-D10
WAd
L
, two 7311-D10
WAd
L
, four 7311-D10
WAd
<L
>
pA
m
<L
>
pA
m
<L
>
pA
m
Install/Air Flow: Maintaining service clearance allows proper air flow.
Service Clearances
1. See page 202 for definitions of noise emissions positions. See noise emissions note 4.
2. Inrush currents occur only at initial application of power, no inrush occurs during normal
power off-on cycle.
3. The upper limit of the dry bulb temperature must be derated 1°C per 137 m (450 ft.) above
915 m (3000 ft.).
4. The upper limit of the wet bulb temperature must be derated 1°C per 274 m (900 ft. ) above
305 m (1000 ft.).
3, 4
1, 4
, one 7311-D10
, two 7311-D10
, four 7311-D10
7311-D10
170 mm (6.6 in)
220 mm (8.7 in)
711 mm (28.0 in)
16.8 kg (37 lbs)
0.21 kVA
200 to 240 V ac, (dc not supported)
50 or 60 Hz
461 Btu/hr
683 Btu/hr
135 watts
200 watts
0.91
64 amps
3048 m (10000 ft.)
Operating
Non-Operating
10 to 38°C
1 to 60°C
50 to 100°F)
(34 to 140°F)
Operating
Non-Operating
8 to 80%
8 to 80%
23°C (73°F)
27°C (81°F)
Operating
Idle
5.6 bels
5.6 bels
5.9 bels
5.9 bels
6.2 bels
6.2 bels
40 dBA
40 dBA
43 dBA
43 dBA
46 dBA
46 dBA
See 7014 Model T00 and T42 Rack for T00 or T42 rack
service clearances.
Chapter 1. Reference Information
Two 7311-D10s with
Enclosure
178 mm (7.0 in)
445 mm (17.5 in)
711 mm (28.0 in)
39.1 kg (86 lbs)
Storage
1 to 60°C
(34 to 140°F)
Storage
8 to 80%
29°C (84°F)
37