8.2 Procedure for switching on

1.
Switch the main power on at the power supply or connect the 24 V to the 24 V supply
board.
2.
The internal buzzer will sound and the product code will be displayed on the LCD
screen along with the revision of host firmware, firmware code and the creation date
of the firmware.
If the above does not occur, DO NOT proceed. Check that the mains supply is
present and that the fuses are good.
3.
Switch the battery On/Off switch to the ON position (230 V model only).
4.
Check that the battery float voltage is 27.6 V. If the voltage is significantly less, then
check:
5.
If there are visible signs of the power supply overheating, then do not proceed.
Disconnect the field wiring and batteries, and eliminate the cause of the problem.
6.
The fire panel will perform internal checks. Any failures occurring will be reported on
the LCD screen.
Observe the total number of faults reported on line 8 of the LCD screen.
It is expected to have at least two faults reported:
7.
Use the
8.
All faults (except for the two above) should be eliminated before proceeding further.
Use the [RESET] button to obtain a new fault report each time.
Possible faults that can occur on switch ON are:
9.
Enable the loop devices of the FP2000 fire panel in one of three methods:
10. Eliminate any fire alarms and communications alarms reported.
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
Are the batteries flat?
Are there possible overloads in the field?
Memory unlocked
Service switch ON
key to view the faults existing.
y Loop overload
y Earth fault
y Battery fail
y Sounders or fire brigade
y Short circuit or open circuit termination resistors
y Specific device faults
y Double address
Individually manually using the Device Set-up Menu.
Set default using the System Default Set-up.
Program by means of a laptop computer using the RS232 port.
- Check the affected loop for short circuits
- Check/eliminate the fault
- Check battery charging
- Check 3K3 termination resistors
- Check device
- Note address of device and check
53