Panel & Repeater Layout; Figure 3: Panel Layout - Interlogix FP 2000 Series Installation And Commissioning Manual

Table of Contents

Advertisement

CAUTION! Mains wires (230 V) must enter the cabinet from the right bottom hole in the
cabinet only. Top entry violates IEC950 safety requirements and will cause EMC
problems.
Mains wires must not be routed past the electronic modules in the rear of the panel. It
must be kept as short as possible and routed directly to the mains input.
4.1.3
Panel & repeater layout
Figure 3:
A.
FP1216EN &
FP1264
B. FR1200 & FR2000
1. Transformer
2. Battery link
3. Battery terminal (+) (red)
4. Mains terminal block
5. Earth stud
6. Main fuse and switch
7. Batteries 12V (2x) (optional)
8. Zone matrix display board (bottom) (optional)
9. Common LED board
10. Service commission mode select
11. Non-volatile memory lock
12. Memory back-up battery jumper
13. Numeric keypad
14. LCD display
15. Current loop terminals
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
Panel layout
16. Host CPU board
17. DB-9 port
18. RS232 and current loop routing of wires
19. ARCNET network card (top) (optional)
20. Battery terminal (-) (black)
21. Battery and power supply connection terminals
22. Modem (MOD2000) power supply terminals
23. Front-end processor board
24. Power supply board
25. Fault relay connections
26. Auxiliary power connections
27. Loop 1-4 terminal connections
28. 2 Loop driver board
29. Sounder relay board
30. Modem (MOD2000) (optional)
31. ARCNET network card (bottom) (NC2011)