3 T
3.1 General specifications
Loop capacity:
•
Every loop PCB (LC2002) can be configured as two class A loops or four class B
loops. (Except FP1200-00 2A/4B or 4A/4B; FP1200-01 2A/2B; FP1200-02 2A/2B)
•
Addressable devices per loop: 126 (900 Series) or 128 (2000 Series)
•
Maximum 1008 (900 Series) or 1024 (2000 Series) addressable devices per panel
•
Maximum eight loops per panel (FP2000 range only)
•
Loop overload: >500 mA
•
Loop operating load: 100 mA maximum
Zone capacity:
•
16 or 64 zones (expandable to 32/128, 48/192 or 64/255 zones in cabinet size B)
•
112 zones for control purposes
LCD screen:
•
Backlit alphanumeric 8 x 40 character LCD
Indicators:
•
General indicators
•
Control indicators
•
Sounders indicators
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
ECHNICAL SPECIFICATIONS
Fire
Fault
Disable
Supply fault
System fault
Processor running
Supply On
Silence buzzer
Disable
Test
Third source test
Sound
Delay On
Delay Off
Fault/Disable
Silence
- 2 x LED - Red
- 1 x LED - Amber
- 1 x LED - Amber
- 1 x LED - Amber
- 1 x LED - Amber
- 1 x LED - Green
- 1 x LED - Green
- 1 x LED - Amber
- 1 x LED - Amber
- 1 x LED - Amber
- 1 x LED - Amber
- 1 x LED - Red
- 1 x LED - Amber
- 1 x LED - Amber
- 1 x LED - Amber
- 1 x LED - Amber
9