Supervised Outputs A; Relay Outputs B; Figure 20: Supervised Relay Output's Connection On Sd2000 Common I/O Board; Figure 21: Two Configurations For Relay Outputs 1-3 B - Interlogix FP 2000 Series Installation And Commissioning Manual

Table of Contents

Advertisement

6.2.3

Supervised outputs A

These outputs provide 24 VDC when active. A red LED displays the state of the outputs.
(Refer to sections 3.2.1 and 3.2.3 for technical information on these outputs.)
Figure 20:
1. Fault routing (Out4)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
* Active in normal position
2. Fire protection device (Out3)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
6.2.4

Relay outputs B

OUT1 / OUT2 / OUT3 (Refer to positions 7, 8, 9 in figure 13.)
Two configurations are available. The configuration is determined by jumper settings.
An LED indicates the state of the output (LED ON = output active).
Figure 21:
Sounders
Fire Brigade
Fire Protection
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
Supervised relay output's connection on SD2000 common I/O board
Two configurations for relay outputs 1-3 B
Outputs
CONFIG. 1
OUT 1
J12 in
J13 out
OUT 2
J2 in
J3 out
OUT3
J4 in
3. Fire routing device (Out2)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
4. Fire alarm device (Out1)
* Termination resistor - 3k3
* Including relay coil resistance
* Polarity non-reversed
CONFIG. 2
"
J12 out
J13 in
"
J2 out
J3 in
J4 out
J18 out
J19 out
J18 out
J19 out
31