6.6.3
FP/FBP/FRL700 Serial communication network
(LON2000)
The LON2000 interface module can be used on the following range of panels: FP2xxx,
FP12xx, FP1xxx, FB2xxx and UN2011 series of products. (Please note that this module
is not for use on any type of repeater e.g. FR2xxx series of products.) The LON2000
interface module provides the hardware platform for the above mentioned products to
communicate to the FP700 range of serial communication interfaces.
The FC1200/2011 board has a 20-pin male connector pin on which the LON2000 board
must be mounted. The PCB is delivered with the necessary washer, nut and spacer to
allow for proper mounting.
Figure 37:
1. FC1200/2011
2. LON2000
Figure 38:
1. LON2000
2. Service switch
3. FBP/FRL700 1 or FP700 module
4. FBP/FRL700 2 or FP700 module
Jumper in Terminated (T) position: Serial communication port is terminated into 120 ohm
Jumper removed: Serial Communication Port is not terminated.
If a LON2000 interface board is used in the first or last panel of a LON network, the
jumper has to be set to (T)erminated.
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
Mounting position of LON2000 board
3. Data + (D+)
4. Data - (D-)
FP1xxx/2xxx Lon port terminal connections
5. Data + (D+)
6. Data - (D-)
7. Termination