6.2.7

Connection of dual tone siren AS263/AS264

The Aritech dual-tone siren can be connected on Sounder (out 1) and Fire Brigade (out 2)
in the following way:
Figure 26:
1. Common
2. Sound
3. Sound
Set jumpers as follows:
"
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
Dual tone siren connections
J2 in, J3 in, J18 in, J19 in
This set-up should only be used when operation mode is "EP"
(see Appendix B).
4. Out2
5. Out1