Panel Operation - Interlogix FP 2000 Series Installation And Commissioning Manual

Table of Contents

Advertisement

3.2.4

Panel Operation

Battery operation - Normal operation
(No mains power)
Current required by system
Loop current
- 2 loops
- 127 devices/loop @ 340 µA/device (DP951)
Auxiliary current
Total normal current
Battery Operation - Alarm Operation
(No mains power)
Normal current (as above)
Extra loop current (20 x LED @ 4 mA)
Sounders (Sounder board: Outputs 1-4)
Total alarm current
Normal Operation
Mains load (maximum)
Total output current (27.6 V)
Battery capacity I
= 0 (72H standby)
AUX
Battery capacity (maximum)
Required battery charging current
(Maximum battery capacity)
Current required by system (I
Available auxiliary current
Alarm Operation
Mains load (maximum)
Total output current (27.6 V)
Required battery charging current
(Maximum battery capacity)
Current required by system
Available auxiliary current
*I
calculated at 252 x 900 series ionisation detectors (FP2416/64) 1008 x 900 series ionisation detectors
SYS
(FP2864/255)
Charging current based to charge batteries up to 80% in 24 hours at 75% efficiency
14
200 mA (max)
86 mA
0 mA
286 mA
286 mA (max)
80 mA
200 mA
566 mA
FP2416/2464 & FP2432/24128
200 VA
4 A
36 AH
69 AH
3.05 A
)*
0.5 A
SYS
0.45 A
FP2416/2464 & FP2432/24128
200 VA
4 A
0 A
0.6 A
3.4 A
FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
FP12XX
FR1200/FR2000
200 mA (max)
0 mA
0 mA
200 mA
FP12XX
FR1200/FR2000
200 mA (max)
0 mA
0 mA
200 mA
200 VA
4 A
58 AH
69 AH
3.05 A
0.8 A
0.15 A
200 VA
4 A
0 A
1 A
3 A
FP1216EN &
FP1264
200 mA (max)
86 mA
0 mA
286 mA
FP1216EN &
FP1264
286 mA (max)
80 mA
200 mA
566 mA
FP2864, FP28255
FP2864, FP28255