SECTION 2 CompoWay/F Communications Procedures

2.4 Response Code List

Normal Completion
Response
code
0000
Normal completion
Error Occurred
Response
code
0401
Unsupported command
1001
Command too long
1002
Command too short
1101
Area type error
1103
Start address out-of-range error
1104
End address out-of-range error
1003
Number of elements/data mis-
match
110B
Response too long
1100
Parameter error
3003
Read-only error
2203
Operation error
2-26
Name
No errors were found.
Name
The service function for the relevant command is
not supported.
The command is too long.
The command is too short.
Wrong variable type
The read/write start address is out of range.
The write end address (write start address +
number of elements) exceeds the final address
of the variable area.
The amount of data does not match the number
of elements.
The response length exceeds the communica-
tions buffer size (when the number of elements
is greater than the maximum number of ele-
ments for that service).
• Bit position is not "00."
• The write data is out of the setting range.
• The command code or related information in
the operation command is wrong.
Variable type "C0" was written to.
• The Communications Writing parameter is set
to "OFF" (disabled).
• Attempted to write to a parameter in setup
area 1 from setup area 0.
• Attempted to write to a protect parameter from
other than the protect level.
• Writing was carried out during AT execution.
• Processing is not possible by operation com-
mand.
• EEPROM error
Description
Description
Error
detection
priority
None
Error
detection
priority
1
2
3
4
5
6
7
8
9
10
11