Response Code List - Omron E5C-T Series Communications Manual

Digital temperature controllers programmable type
Table of Contents

Advertisement

2 CompoWay/F Communications Procedures
2-4

Response Code List

Normal Completion
Response code
0000
Error Occurred
Response code
0401
1001
1002
1101
1103
1104
1003
110B
1100
3003
2203
2 - 22
Name
Normal completion
Name
Unsupported command
Command too long
Command too short
Area type error
Start address out-of-range
error
End address out-of-range
error
Number of elements/data
mismatch
Response too long
Parameter error
Read-only error
Operation error
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
Description
No errors were found.
Description
The service function for the relevant command is not
supported.
The command is too long.
The command is too short.
Wrong variable type
The read/write start address is out of range.
The write end address (write start address + number of
elements) exceeds the final address of the variable area.
The amount of data does not match the number of
elements.
The response length exceeds the communications buffer
size (when the number of elements is greater than the
maximum number of elements for that service).
• Bit position is not "00."
• The write data is out of the setting range.
• The command code or related information in the
operation command is wrong.
Variable type "C0" was written to.
• The Communications Writing parameter is set to "OFF"
(disabled).
• Attempted to write to a parameter in setup area 1 from
setup area 0.
• Attempted to write to a protect parameter from other than
the protect level.
• Writing was carried out during AT execution.
• Processing is not possible by operation command.
• Non-volatile memory error
Error detection
priority
None