Test Signals; Tripping Speed Test ( ∆ T) - Fluke 165X Installation Manual

Electrical installation tester
Hide thumbs Also See for 165X:
Table of Contents

Advertisement

165X
Users Manual

Test Signals

RCD Type
AC
The waveform is a sinewave starting at zero crossing, polarity determined by phase selection (0º
phase starts with low to high zero crossing, 180º phase starts with high to low zero crossing). The
magnitude of the test current is I
A
The waveform is a half wave rectified sinewave starting at zero, polarity determined by phase
selection (0º phase starts with low to high zero crossing, 180º phase starts with high to low zero
crossing). The magnitude of the test current is 2.0 x I
magnitude of the test current is 1.4 x I
Tripping Speed Test ( ∆ T)
Model 1651
Current Settings
10–30–100–300-500-1000 mA
10–30–100–300-500-1000 mA
*G – General, no delay
*S – Time delay
52
Test Signal Description
n x Multiplier for all tests.
n x Multiplier for all tests for all other I
Multiplier
Current Accuracy
x 1
+10% -0%
x 1
+10% -0%
n x Multiplier for all tests for I
n ratings.
*RCD Type
G
S
n = 0.01A. The
Maximum Test
Time
310 ms
510 ms