To enter Memory mode
Press the M button to enter Memory mode. The
1.
display changes to a memory mode display. In
Memory mode, the N icon appears on the
display. The primary numeric display will be active
with the left two digits (a) indicating the data set
number (1-99) and the right two digits (b) indicating
the data subset number. The decimal point separating
these two values will be active. The secondary
numeric display (c) will be active indicating the data id
number (1-500). The memory locations (a, b, or c) will
flash, indicating that you can change the number
using the arrow keys U.
2.
To enable the data subset number to be changed,
press 1. The data subset number will now be
flashing. To enable the data sub number to be
changed, press 1 again. The data set number will
now be flashing. Press 1 again to change the data id
number.
3.
Press the down arrow key (U) to decrement the
enabled number or press the up arrow key (U) to
increment the enabled number. For storing data, the
number can be set to any value, overwriting existing
data is allowed. For recalling data, the number can
only be set to used values.
Storing and Recalling Measurements (Model 1653 Only)
If you press the up or down arrow key ( U ) once,
the number increments or decrements by one. If
you press and hold the up or down arrow, the
numbers increment or decrement quickly by
approximately 10 digits per second.

Storing a Measurement

To store a measurement
Press M to enter Memory mode.
1.
Press 1 and use the arrow keys (U) to set the data
2.
identity.
Press 2 to save the data.
3.
If memory is full, FULL will appear on the primary
display. Press 1 to choose another data identity,
press M to exit Memory mode.
If the memory is not full, the data will be saved,
the tester will automatically exit Memory mode
and the display will revert back to the previous
test mode.