Line Speed Input Setting (Pr. 763 To Pr. 768) - Mitsubishi Electric FR-A700-A1 Instruction Manual

Dancer control function/tension control function
Table of Contents

Advertisement

3.8.2

Line speed input setting (Pr. 763 to Pr. 768)

(1)
Line speed input selection (Pr. 763)
Select input terminal of line speed command to perform winding diameter calculation.
When material thickness is set to Pr. 752 Material thickness d1 (Pr. 752
speed but from the addition of material thickness and rotation number of a roll, but not from line speed. (Refer to page 35).
Pr.763 Line speed input
selection
0 (initial value)
1
2
3
4
5
6
7
*1
Not available during vector control.
*2
To switch among 0 to 5VDC, 0 to 10VDC, and 0 to 20mA, use Pr. 73 setting as well as voltage/current input switch. (Refer to the Instruction Manual for
details.)
*3
To switch among 0 to 20mA, 0 to 10VDC, and 0 to 5VDC, use Pr. 267 setting as well as voltage/current input switch. (Refer to the Instruction Manual for
details.)
(2)
Unit conversion for line speed (Pr. 764, Pr. 765, Pr. 766, Pr. 767)
Convert pulse input unit (kpps) and analog input unit (%), which are selected in Pr.763 Line speed input selection, to line
speed unit (mm(m)/min(sec)).
Parameter
Number
Pulse reference for line
764
speed input
Voltage reference for line
765
speed input
766
Line speed reference
767
Line speed unit
(3)
Input filter (Pr. 768)
Set the time constant of the first-order lag filter. Set a large time constant when you want to delay the tracking of the
speed command, and when the analog input voltage fluctuates, etc.
Filters can be applied to pulse train input when Pr. 763 = "1, 2 or 7" by using Pr. 768 Line speed input filter time constant.
Filters can be applied to analog input with input filter time constant of Pr. 74 when Pr. 763 = "3, 4, 5 or 6".
Parameter
Number
Line speed input filter
768
time constant
Unit
Pulse (kpps)
Voltage (V)/ Current (mA)
pulse [kpps]
Name
Setting Range
0.01 to 200kpps
0.1 to 100%
1.0 to 6553.4
0, 1, 2, 3
Name
Setting Range
0 to 5s
Winding diameter compensation
"9999"), calculate winding diameter not from line
Line speed input terminal
— (Calculate line speed from main speed)
Terminal JOG single-phase pulse train input
FR-A7AP connection: encoder pulse input
(24V open collector/5V differential (A, B phase))
Terminal 2 input (analog value 0 to 100%)
Terminal 4 input (analog value 0 to 100%)
Terminal 1 (analog value 0 to 100%)
Terminal 6 (analog value 0 to 100%) (FR-A7AZ)
FR-A7AL connection: single-phase pulse train input
Increments
0.01kpps
0.1%
0.1
1
Increments
0.001s
function
*1
*2
*3
Initial Value
Remarks
30kpps
50%
1000.0
0 : m/min
1 : m/sec
0
2 : mm/min
3 : mm/sec
Initial Value
Remarks
0.025s
0: without filter
3
33