The gas appliance and vent system must be vented directly to the outside of the building, and
never be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each
direct vent gas appliance must use it's own separate vent system.
In addition to the requirements listed here, follow the requirements provided with the vent.
A firestop is required whenever the vent penetrates a wall, floor, or ceiling (passes through
framing members). Horizontal vent less than 48" above the fireplace must use the Travis
Firestop (sku 93006094 - it incorporates a 3" clearance above, 1" clearance below and to the
sides of the vent). Other penetrations only require a 1" clearance and may use a standard
firestop (make sure the required 1" clearance is met).
Always use the high-wind termination (if available from the vent manufacturer).

Vent Clearances

The vent must maintain the required clearance to combustible materials to prevent a fire. Do
not fill air spaces with insulation.
Sides
Above
Below Horizontal or 45° Section
Vertical Termination
Use a roof flashing and storm collar
whenever passing through the roof
Use a firestop whenever
passing through a ceiling
Use a support box
on exposed vent

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 6,000 feet. In this testing we have found
that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.
© Travis Industries
Installation
(for qualified installers only)
Before 48" Rise
1"
3"
1"
Required Firestop
Min. 1"
4080214
After 48" Rise
1"
1"
1"
Horizontal
Termination
Min. 3"
(1" if a minimum 48"
above the fireplace)
Min. 1"
Min. 1"