Swing Flap Motor Malfunction / Lock

A7
Remote
Controller
Display
Applicable
FHQ-BU
Models
Method of
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Detection
Malfunction
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
Decision
motor is energized for a specified amount of time (about 30 seconds).
Conditions
Supposed
Causes
Troubleshooting
Failure of motor
Failure of microswitch
Failure of connector connection
Failure of indoor unit PCB
Troubleshooting for SkyAir Indoor Unit