Daikin Super Multi Plus D-Series Service Manual page 297

Table of Contents

Advertisement

Troubleshooting for SkyAir Indoor Unit
Check No. 02
Check for Thermistors
Disconnect the thermistor connector from PCB, then measure the resistance by using a tester.
Thermistor temperature and resistance characteristics
Temperature
Application
286
A
°C
-6.0
90.8
-4.0
81.7
-2.0
73.5
0.0
66.3
2.0
59.8
4.0
54.1
6.0
48.9
8.0
44.3
10.0
40.2
12.0
36.5
14.0
33.2
16.0
30.2
18.0
27.5
20.0
25.1
22.0
23.0
24.0
21.0
26.0
19.2
28.0
17.6
30.0
16.2
32.0
14.8
34.0
13.6
36.0
12.5
38.0
11.5
40.0
10.6
42.0
9.8
44.0
9.1
46.0
8.4
48.0
7.8
50.0
7.2
52.0
6.9
54.0
6.2
56.0
5.7
58.0
5.3
Heat exchanger
(Indoor/Outdoor units)
Suction air
Remote controller
Air
Outdoor air
Suction pipe
Unit : kΩ
B
88.0
79.1
71.1
64.1
57.8
52.3
47.3
42.9
38.9
35.3
32.1
29.2
26.6
24.3
22.2
20.3
18.5
17.0
15.6
4.2
13.1
12.0
11.1
10.3
9.5
8.8
8.2
7.6
7.0
6.7
6.0
5.5
5.2
Radiator fin
SiEBE18-526