Daikin Super Multi Plus D-Series Service Manual page 240

Table of Contents

Advertisement

SiEBE18-526
Be sure the air conditioner is electrically grounded.
Do not connect the grounding conductor to a gas pipe,
water pipe, lightning arrester, and the grounding
conductor for a telephone.
Imperfect grounding work may result in an electric shock.
Execute complete drain piping for perfect
drainage.
Incomplete piping may result in a water leakage.
The appliance is not intended for use by
young children or infirm persons without
supervision.
Young children should be supervised to ensure
that they do not play with the appliance.
3. OPERATION RANGE
If the temperature or the humidity is beyond the following
conditions, safety devices may work and the air conditioner
may notoperate, or sometimes, water may drop from the
indoor unit.
COOLING
OUTDOOR UNIT
TEMPERA-
TURE
DB
R35 · 45 · 60
WB
DB
RY35 · 45 · 60
WB
R71 · 100 · 125
DB
RP71 · 100 · 125
WB
REP71 · 100 · 125
RY71 · 100 · 125
DB
RYP71 · 100 · 125
WB
RYEP71 · 100 · 125
DB
RZP71 · 100 · 125
WB
DB
RQ71 · 100 · 125
WB
DB
RR71 · 100 · 125
WB
DB
RZQ71 · 100 · 125 ·
140
WB
RS50 · 60
DB
RKS35 · 50 · 60
RXS35 · 50 · 60
WB
3MKS50
DB
4MKS58 · 75 · 90
3MXS52 · 2MXS52
WB
4MXS68 · 80
DB
RMKS112 · 140 · 160
RMXS112 · 140 · 160
WB
System Configuration
INDOOR
OUTDOOR
TEMPERA-
HUMID-
TURE
ITY
18 to 33
80% or
DB
– 15 to 46
below
12 to 24
18 to 33
80% or
DB
– 5 to 46
below
12 to 24
21 to 35
80% or
DB
– 15 to 46
below
14 to 25
18 to 35
80% or
– 5 to 46
DB
below
12 to 25
21 to 35
80% or
DB
– 5 to 50
below
14 to 25
18 to 37
80% or
– 5 to 46
DB
below
12 to 28
18 to 37
80% or
– 15 to 46
DB
below
12 to 28
18 to 37
80% or
– 15 to 50
DB
below
12 to 28
21 to 32
80% or
– 10 to 46
DB
below
14 to 23
21 to 32
80% or
– 10 to 46
DB
below
14 to 23
21 to 32
80% or
DB – 5 to 46
below
14 to 23
HEATING
INDOOR
OUTDOOR UNIT
TEMPERATURE
RY35 · 45 · 60
DB
15 to 27
RY71 · 100 · 125
RYP71 · 100 · 125
DB
15 to 27
RYEP71 · 100 · 125
RZP71 · 100 · 125
DB
15 to 27
RQ71 · 100 · 125
10 to 27
DB
RZQ71 · 100 · 125 ·
10 to 27
DB
140
RXS35 · 50 · 60
DB
10 to 30
3MXS52 · 2MXS52
DB
10 to 30
4MXS68 · 80
RMXS112 · 140 · 160
DB
10 to 30
D B: Dry bulb temperature (°C)
WB: Wet bulb temperature (°C)
The setting temperature range of the remote
control is 16°C to 32°C.
4. INSTALLATION SITE
Regarding places for installation
• Is the air conditioner installed at a well-
ventIlated place where there are no obstacles
around?
• Do not use the air conditioner in the following
places.
a. Filled with much mineral oil such as cutting oil
b. Where there is much salt such as a beach
area
c. Where sulfured gas exists such as a hot-
spring resort
d. Where there are considerable voltage fluctua-
tions such as a factory or plant
e. Vehicles and vessels
f. Where there is much spray of oil and vapor
such as a cookery, etc.
g. Where there are machines generating electro-
magnetic waves
h. Filled with acid and/or alkaline steam or vapor
• Is a snow protection measure taken?
For details, consult your dealer.
Regarding wiring
• All wiring must be performed by an autho-
rized electrician.
To do wiring, ask your dealer. Never do it by yourself.
Instruction
OUTDOOR
TEMPERATURE
– 9 to 21
DB
– 10 to 15.5
WB
DB
– 9 to 21
– 10 to 15.5
WB
– 14 to 21
DB
– 15 to 15.5
WB
– 9 to 21
DB
– 10 to 15
WB
– 19.5 to 21
DB
– 20 to 15.5
WB
– 14 to 24
DB
– 15 to 18
WB
– 14 to 21
DB
– 15 to 15.5
WB
DB
– 14 to 21
WB
– 15 to 15.5
229