Daikin Super Multi Plus D-Series Service Manual page 270

Table of Contents

Advertisement

SiEBE18-526
Troubleshooting
Check No.06
Refer to P.266
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the air passage.
Is there any
short-circuit?
NO
Check the intake air filter.
Is it very dirty?
NO
Check the dust accumulation on
the indoor unit heat exchanger.
Is it very dirty?
NO
Check No. 06
Indoor unit heat exchanger
thermistor check
Does it conform to
the thermistor characteristic
chart?
NO
YES
YES
YES
YES
Troubleshooting for RA Indoor Unit
Provide sufficient air passage.
Clean the air filter.
Clean the heat exchanger.
Replace the indoor unit PCB.
Replace the thermistor
(replace the indoor unit PCB).
(R4695)
259

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents