LG ARUV Series Service Manual page 260

Multi v plus system
Hide thumbs Also See for ARUV Series:
Table of Contents

Advertisement

Troubleshooting Guide
Error
Error Type
No.
Over-increase discharge
32(Main)
temperature of inverter com-
pressor at main outdoor unit
33 (Main)
100,101
Over-increase discharge
(Sub1)
temperature of constant
compressor at main con-
102,103
stant outdoor and sub con-
(Sub2)
stant outdoor unit
152,153
(Sub3)
Error diagnosis and countermeasure flow chart
Is the amount of
refrigerant normal?
[refer refrigerant part]
Yes
Is the resistance of discharge
temperature sensor normal?*
Yes
Is LEV in
outdoor unit normal
at heating operation?
[refer electric
component part]
Yes
Does liquid injection
corresponded
operate normally?
Yes
Is there pipe
(strainer etc.) clogging?
Yes
Replace strainer
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Error Point
Compressor is off
because of over-increase
discharge temperature of
inverter compressor
Compressor is off
because of over-increase
discharge temperature of
constant compressor at
main and sub outdoor unit
No
Is there pipe crack
or trace of leakage?
Yes
Weld / reconnect the cracked
portion and recharge refrigerant
No
Replace discharge
temperature sensor
* Resistance value of discharge temperature sensor
10°C = 362kΩ, 25°C= 200kΩ, 50°C= 82kΩ, 100°C= 18.5kΩ
No
Replace outdoor unit LEV
No
Check liquid injection
corresponded
Check another components
No
and operation conditions
/ Take measures
- 260 -
Main Reasons
1. Temperature sensor defect of inverter com-
pressor discharge pipe
2. Refrigerant shortage / leak
3. LEV defect
4. Liquid injection valve defect
1. Temperature sensor defect of constant
compressor discharge pipe?
2. Refrigerant shortage/leak
3. LEV defect
4. Liquid injection valve defect
Change the amount of
No
refrigerant
(Charge additive amount)
LGE Internal Use Only