1.3 Main and sub unit's EEV control

(1) Main EEV control
Main EEV operates with fuzzy control rules to keep the degree of super Heat(Superheat) (about 3°C)at
the evaporator outlet stable during heating mode
The degree of Superheat = Tsuction - Tevaporation
Tsuction : temperature at suction pipe sensor(°C)
Tevaporation : evaporation temperature equivalent to low pressure(°C)
(2) Sub EEV control
Sub EEV operates according to the opening of main EEV, otherwise the opening range is limited by the
open degree of the main EEV
- Limited conditions : liquid back control, discharge temperature control etc.
(3) Subcooling EEV control(about 15°C)
Subcooling EEV works with fuzzy rules to keep the degree of Subcool at the outlet of subcooler during
cooling mode
The degree of Subcool = Tcondensation - Tliquid
Tliquid : temperature at outlet of subcooler(°C)
Tcondensation : condensation temperature equivalent to high pressure(°C)
(4) Avoiding excessive high discharge temperature : when main EEV opens some given opening (R22 :
1000pls, R410A : 800 pls) and discharge temperature is above 85°C in heating operation, subcooling
EEV may control the "subcooling out temperature-evaporating temperature" to be some given difference.