Troubleshooting Guide - LG ARUV Series Service Manual

Multi v plus system
Hide thumbs Also See for ARUV Series:
Table of Contents

Advertisement

Troubleshooting Guide

Error
Error Type
No.
01
Indoor unit air sensor error
02
Indoor unit pipe inlet sensor error
06
Indoor unit pipe outlet sensor error
Error diagnosis and countermeasure flow chart
Is sensor properly
connected to PCB?
Yes
Is the resistance value
of sensor normal?*
Yes
Change the PCB
** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin)
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Indoor unit sensor is
No
Connect properly to PCB
No
Change the sensor
: 25°C= 5kΩ : 50°C= 1.8kΩ
- 246 -
Error Point
1. Indoor unit PCB wrong connection
2. Indoor unit PCB failure
open/short
3. Sensor problem (main reason)
Normal
CN-ROOM : Indoor air temp sensor
CN-PIPE2 : Pipe outlet temp sensor
CN-PIPE1 : Pipe inlet temp sensor
Measure the resistance of outlet pipe temp sensor.
Main Reasons
LGE Internal Use Only