2.4 Stopping operation

2.4.1 Stopping operation on cooling mode
Component
Inv Compressor
Sub unit
compressor
Fan
Main EEV
4 way valve
Subcooling EEV
Hot gas bypass
2.4.2 Stopping operation on heating mode
Component
Inv Compressor
Sub unit
compressor
Fan
Main EEV
4 way valve
Subcooling EEV
Hot gas bypass
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Operation
0 Hz
Off
0 Hz
Full open
Off
Full close
On
Operation
0 Hz
Off
0 Hz
Full open
On
Full close
On
- 207 -
Note
-
-
-
After 15 min from stop, min.
Off
Full close
After 15 min from stop, Off
Note
-
-
-
After 15 min from stop, min.
After 15 min from stop, off
Full close
After 15 min from stop, Off