1. Basic control

1.1 Normal operation

Actuator
Compressor
Fan
Main EEV
4 way valve
Subcooling
EEV
Note: Heating operation is not functional at an outdoor air temperature of 27°C or more

1.2 Compressor control

Fuzzy control : Maintain evaporating temperature(Te) to be constant on cooling mode and condensing tem-
perature(Tc) on heating mode by Fuzzy control to ensure the stable system performance.
(Tc:47 ~51°C, Te:2 ~ 5°C)
(1) Cooling mode
Te can be set by initial dip switch setting. (Normal mode, capacity up mode, and energy save mode)
(2) Heating mode
Tc can be set by initial dip switch setting. (Normal mode, capacity up mode, and energy save mode)
Note: By setting dip switch, Te and Tc are decided simultaneously.
(1) The sequence of compressor operation for 3 unit system
INV
C1
Main
1) Stage increasing situation
Inv
C3
C5
C2
Inv
C5
C2
C4
Inv
C2
C4
C3
Inv
C4
C3
C5
*Stage means how many constant compressors operate
Example) Stage 2: 2 constant compressors operate
Stage 1: 1 constant compressor operate
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cooling operation
Heating operation
Fuzzy control
Fuzzy control
Full open
Off
• Normal : minimum pulse
• Avoiding control of high
Fuzzy control
discharge temperature
C2
C3
SUB1
C4
C1(full)
C3
C1(full)
C5
C1(full)
C2
C1(full)
Fuzzy control
Fuzzy control
Fuzzy control
On
C4
SUB2
2) Stage decreasing situation
Full
C1
C3
C5
C2
Full
C1
C5
C2
C4
Full
C1
C2
C4
C3
Full
C1
C4
C3
C5
- 197 -
Function
Stop state
stop
stop
After 15min,
min. pulse
After 15min, Off
After 15min,
min. pulse
C5
C4
Inv
C3
Inv
C5
Inv
C2
Inv
LGE Internal Use Only