Operation Details
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Indoor unit
Heat-Exchanger
temperature
Intake Air Temperature
Setting Temperature
(Thermal OFF)
Setting Temperature
(Thermal ON)
Thermal
Outdoor fan
Indoor fan
4way valve
• Compressor-off interval : -
Chassis
Hotstart On
T
On
Hotstart Off
T
Off
Low temperature T
LT
Setting Temperature T
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
40°C
T
ST
T
LT
T
Off
T
On
+3°C
1min
ON
ON
Setting
fan
Off
Low
Low
spped
While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
A
at low speed, when it becomes lower than 40°C fan stops.
-
For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
B
-
C
To be operated "Low" except initial Hotstart operation
High Static
BH
BG
19°C
19°C
22°C
22°C
25°C
25°C
27°C
27°C
ST
3min
Minimum
Setting
fan
Low
Low
spped
ON
Low Static
BR
B1
B2
CE
19°C
19°C 19°C 19°C 19°C
22°C
22°C 22°C 22°C 22°C
25°C
25°C 25°C 25°C 25°C
27°C
27°C 27°C 27°C 27°C
- 158 -
A
Low fan during 10sec
B
1min
3min
OFF
ON
OFF
ON
C
Setting
fan
Off
Off
Low
spped
Convertible
CF
VE
26°C
27°C
28°C
30°C
LGE Internal Use Only
VJ
26°C
27°C
28°C
30°C